Goodrive200L
inverters Basic operation instruction
102
7.5 Parameters of the motor
Physical accident may occur if the motor starts up suddenly during
autotune. Please check the safety of surrounding environment of the
motor and the load before autotune.
The power is still applied even the motor stops running during static
autotune. Please do not touch the motor until the autotune is
completed, otherwise there would be electric shock.
Do not carry out the rotation autotune if the motor is coupled with the
load, please do not operate on the rotation autotune. Otherwise
misaction or damage may occur to the inverter or the mechanical
devices. When carry out autotune on the motor which is coupled with
load, the motor parameter won’t be counted correctly and misaction
may occur. It is proper to de-couple the motor from the load during
autotune when necessary.
The control performance of the inverter is based on the established accurate motor model.
The user has to carry out the motor autotune before first running (take motor 1 as the
example).
Note:
1.
Set the motor parameters according to the name plate of the motor.
2.
During the motor autotune, de-couple the motor form the load if rotation autotune is
selected to make the motor is in a static and empty state, otherwise the result of autotune is
incorrect. The asynchronous motors can autotune the parameters of P02.06~P02.10.
3.
During the motor autotune 1, do not to de-couple the motor form the load if static autotune
is selected. Because only some parameters of the motor are involved, the control
performance is not as better as the rotation autotune. The asynchronous motors can
autotune the parameters of P02.06~P02.10.
4.
During the motor autotune 2, do not to de-couple the motor form the load if static autotune
is selected. Because only some parameters of the motor are involved, the control
performance is not as better as the rotation autotune. The asynchronous motors can
autotune the parameters of P02.06~P02.08. It is suitable in the cases which SVPWM control
is applied.
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...