Goodrive200L
inverters Fault tracking
129
Fault
code
Fault type
Possible cause
What to do
OL3
Electrical overload
The inverter will report
overload pre-alarm
according to the set
value
Check the load and the
overload pre-alarm
point.
ETH1
Grounding shortcut fault 1
The output of the
inverter is short
circuited with the
ground
There is fault in the
current detection
circuit
Check if the
connection of the
motor is normal or not
Change the Hoare
Change the main
control panel
ETH2
Grounding shortcut fault 2
The output of the
inverter is short
circuited with the
ground
There is fault in the
current detection
circuit
Check if the
connection of the
motor is normal or not
Change the Hoare
Change the main
control panel
dEu
Velocity deviation fault
The load is too heavy
or stalled
Check the load and
ensure it is normal
Increase the detection
time
Check whether the
control parameters are
normal