Goodrive200L
inverters Fault tracking
132
Fault
code
Fault type
Possible cause
What to do
E-NET
Ethernet communication
Fault
The Ethernet address
is not set right.
The Ethernet
communication is not
selected to right.
The ambient
interference is too
strong.
Check the relative
setting.
Check the
communication
method selection.
Check the environment
and avoid the
interference.
E-CAN
CANopen communication
fault
Corresponding
resistor is not dial
The communication is
uneven
Check related setting
Set the same baud
rate
Check the environment
and avoid the
interference.
LL
Electronic underload fault
The inverter will report
the underload
pre-alarm according to
the set value
Check the load and the
underload pre-alarm
point
RE
Running contactor
feedback error
Running Contactor
feedback signal lost
Check the circuit or
disable the feedback
signal detection
BE
Brake contactor feedback
error
Brake contactor
feedback signal lost
Check the circuit or
disable the feedback
signal detection
ENC1O
Encoder wire break fault
Encoder fault or wiring
fault
Check the encoder and
the wiring
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...