Goodrive200L
inverters Function parameters
41
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
(valid when P01.21=1)
P01.23
Start delay
time
The function determines the brake release after
the running command is reference, and the
inverter is in a stand-by state and wait for the
delay time set by P01.23
Setting range: 0.0~60.0s
0.0s
○
P01.24
Delay time of
the stop
speed
Setting range: 0.0~100.0 s
0.0s
●
P01.25
0Hz output
selection
0: without voltage output
1: Voltage output
2: The output current of DC braking is in
accordance to stopping.
1
●
P01.26
Feedback
Signal
selection of
running
contactor
0: Signal of running contactor feedback is invalid.
1: Signal of running contactor feedback is valid.
2: Detection feedback signal missing doesn’t call
fault. The inverter testing contactor feedback
signal, when inspection feedback signal and the
time beyond P01.27 feedback check out time,
inverter stop but no RE code.
0
○
P01.27
Detection
time of the
feedback
signal of
running
contactor
When signal of running contactor feedback is
valid (P01.26=1), After the system output the
signal that makes the running contactor close,
but the system still doesn’t detect feedback
signal in P01.27 time, and the system
immediately stop the motor and report the fault of
detection of running contactor feedback signal.
0.0s
○
P01.28
Feedback
Signal
selection of
0:Signal of braking contactor feedback is invalid.
1:Signal of braking contactor feedback is valid.
2: Detection feedback signal missing doesn’t call
0
○
P01 24
.
Output frequency
Stopping speed
In running
T
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...