Goodrive200L
inverters Function parameters
38
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
setting
P01.08 Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to reduce
the output frequency during the set time. When
the frequency decreases to 0Hz, the inverter
stops.
1: Coast to stop: after the stop command
becomes valid, the inverter ceases the output
immediately. And the load coasts to stop at the
mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
Starting frequency of DC braking: start the DC
braking when running frequency reaches starting
frequency determined by P1.09.
Waiting time before DC braking: Inverters block
the output before starting the DC braking. After
this waiting time, the DC braking will be started
so as to prevent over-current fault caused by DC
braking at high speed.
DC braking current:The value of P01.11 is the
percentage of rated current of inverter. The
bigger the DC braking current is, the greater the
braking torque is.
DC braking time: The retention time of DC brake.
If the time is 0, the DC brake is invalid. The
inverter will stop at the set deceleration time.
Setting range of P01.09: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P01.10: 0.00~50.00s
Setting range of P01.11: 0.0~100.0%
Setting range of P01.12: 0.00~50.00s
0.00Hz
○
P01.10
Waiting time
before DC
braking
0.00s
○
P01.11
DC braking
current
0.0%
○
P01.12
DC braking
time
0.00s
○
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV
rotation, set the threshold by P01.14, which is as
the table below:
0.0s
○
P01.23
ACC
Constant
speed
DEC
ON
T
P13.14
P01.04
P01.10
P13.15
P01.12
P01.09
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...