Goodrive200L
inverters Function parameters
43
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
model
P02.06
Stator
resistor of
AM 1
0.001~65.535Ω
Depend
on
model
○
P02.07
Rotor
resistor of
AM 1
0.001~65.535Ω
Depend
on
model
○
P02.08
Leakage
inductance of
AM 1
0.1~6553.5mH
Depend
on
model
○
P02.09
Mutual
inductance of
AM 1
0.1~6553.5mH
Depend
on
model
○
P02.10
Non-load
current of AM
1
0.1~6553.5A
Depend
on
model
○
P02.26
Motor 1
overload
protection
0: No protection
1: Common motor (with low speed
compensation). Because the heat-releasing
effect of the common motors will be weakened,
the corresponding electric heat protection will be
adjusted properly. The low speed compensation
characteristic mentioned here means reducing
the threshold of the overload protection of the
motor whose running frequency is below 30Hz.
2: Variable frequency motor (without low speed
compensation) Because the heat-releasing effect
of the specific motors won’t be impacted by the
rotation speed, it is not necessary to adjust the
protection value during low-speed running.
2
◎
P02.27
Motor 1 over
load
protection
coefficient
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the
output current of the inverter and K is the motor
protection coefficient.
So, the bigger the value of K is, the smaller the
value of M is. When M =116%, the fault will be
reported after 1 hour, when M =200%, the fault
will be reported after 1 minute, when M>=400%,
the fault will be reported instantly.
100.0%
○
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...