Goodrive200L
inverters Function parameters
54
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
BIT3:S4
virtual terminal
BIT4:S5
virtual terminal
BIT5:S6
virtual terminal
BIT6:S7
virtual terminal
BIT7:S8
virtual terminal
BIT8:HDI
virtual terminal
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines
the rotation direction by the defined FWD and
REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Hold
Forward
running
Rev running
1:2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the
state of the defined REV.
2:3-wire control 1; Sin is the enabling terminal on
this mode, and the running command is caused
by FWD and the direction is controlled by REV.
Sin is natural closed.
The direction control is as below during
0
◎
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...