Goodrive200L
inverters Installation guidelines
18
Fig 4-14 220~315kW terminals of main circuit
Fig 4-15 350~500kW terminals of main circuit
Terminal
Terminal name
Function
≤30kW
≥37kW
R, S, T
Power input of the main circuit
3-phase AC input terminals which are
generally connected with the power
supply.
U, V, W
The inverter output
3-phase AC output terminals which are
generally connected with the motor.
P1
This terminal is
inexistent
DC reactor terminal 1 P1 and (+) are connected with the
terminals of DC reactor.
(+) and (-) are connected with the
terminals of braking unit.
PB and (+) are connected with the
terminals of braking resistor.
(+)
Braking resistor
1
DC reactor terminal 2,
braking unit terminal 1
(-)
/
Braking unit terminal 2
PB
Braking resistor
terminal 2
This terminal is
inexistent.
PE
380V:the grounding resistor is less
than 10Ohm
Protective grounding terminals, every
machine is provided 2 PE terminals as
the standard configuration. These
terminals should be grounded with
proper techniques.
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...