Goodrive200L
inverters Function parameters
73
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
time from the highest point to the lowest one.
The setting range of P08.15: 0.0~100.0%
(relative to the set frequency)
The setting range of P08.16: 0.0~50.0%
(relative to the traverse range)
The setting range of P08.17: 0.1~3600.0s
The setting range of P08.18: 0.1~3600.0s
P08.19
Setting
length
The function codes of setting length, actual
length and unit pulse are mainly used to control
the fixed length.
The length is counted by the pulse signal of HDI
terminals input and the HDI terminals are needed
to set as the length counting input.
Actual length
=
the length counting input pulse
/
unit pulse
When the actual length P08.20 exceeds the
setting length P08.19, the multi-function digital
output terminals will output ON.
Setting range of P08.19: 0~65535m
Setting range of P08.20:0~65535m
Setting range of P08.21:1~10000
Setting range of P08.22:0.01~100.00cm
Setting range of P08.23:0.001~10.000
Setting range of P08.24:0.001~1.000
0m
○
P08.20 Actual length
0m
●
P08.21
Pulse per
rotation
1
○
P08.22
Alxe
perimeter
10.00
cm
○
P08.23 Length ratio
1.000
○
P08.24
Length
correcting
coefficient
1.000
○
P08.25
Setting
counting
value
The counter works by the input pulse signals of
the HDI terminals.
When the counter achieves a fixed number, the
multi-function output terminals will output the
signal of “fixed counting number arrival” and the
counter go on working; when the counter
achieves a setting number, the multi-function
output terminals will output the signal of “setting
counting number arrival”, the counter will clear all
numbers and stop to recount before the next
pulse.
The setting counting value P08.26 should be no
more than the setting counting value P08.25.
The function is illustrated as below:
0
○
P08.26
Reference
counting
value
0
○
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...