Goodrive200L
inverters Function parameters
36
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
power file than that of P type.
P00.18
Function
restore
parameter
0:No operation
1:Restore the default value
2:Clear fault records
Note:
The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0
◎
P01 Group Start-up and stop control
P01.00
Start running
form
0:Start-up directly
1:Start-up after DC braking
2:Start-up after speed tracking 1.
3:Start-up after speed tracking 2
0
◎
P01.01
The start
frequency of
direct start
running
Starting frequency of direct start-up means the
original frequency during the inverter starting.
See P01.02 for detailed information.
Setting range: 0.00~50.00Hz
0.00Hz
◎
P01.02
The start
frequency
holding time
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the
output frequency of the inverter is the starting
frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the inverter will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
Setting range: 0.0~50.0s
0.0s
◎
P01.03
The braking
current
The inverter will carry out DC braking at the
braking current set before starting and it will
0.0%
◎
fmax
t1
f1 set by P01 01
.
f1
t1 set by P01 02
.
Output frequency
T
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...