![INVT GD200L-004G-4 Скачать руководство пользователя страница 121](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737121.webp)
Goodrive200L
inverters Basic operation instruction
116
P10.14
Multi-step
speed6
Multi-step speed6
0~Max
frequency
○
0.0 HZ
P10.16
Multi-step
speed7
Multi-step speed7
0~Max
frequency
○
0.0 HZ
P10.18
Multi-step
speed8
Multi-step speed8
0~Max
frequency
○
0.0 HZ
P10.20
Multi-step
speed9
Multi-step speed9
0~Max
frequency
○
0.0 HZ
P10.22
Multi-step
speed10
Multi-step speed10
0~Max
frequency
○
0.0 HZ
P10.24
Multi-step
speed11
Multi-step speed11
0~Max
frequency
○
0.0 HZ
P10.26
Multi-step
speed12
Multi-step speed12
0~Max
frequency
○
0.0 HZ
P10.28
Multi-step
speed13
Multi-step speed13
0~Max
frequency
○
0.0 HZ
P10.30
Multi-step
speed14
Multi-step speed14
0~Max
frequency
○
0.0 HZ
P10.32
Multi-step
speed15
Multi-step speed15
0~Max
frequency
○
0.0 HZ
7.
Motor Parameters Autotuning
When it is not clear about the resistor and the inductance of motor, it must do motor
parameter autotuning:
Set P00.15=1 then press the RUN to start the rotation autotuning, and the situation can
apply to disconnect the load.
Set P00.15=2 then press the RUN to start the static autotuning, and the situation can apply
to connect the load.
(Generally the motor stator resistor from autotuning is accuracy and the motor inductance
from autotuning is inaccuracy, so if it knows the motor factory parameter, we suggest
adopting to the value of the motor stator resistor from autotuning, and the motor inductance
still use the motor factory parameters.)
After autuning, set P00.00=0. In order to debugging, we define the direction of elevator going
up as the right direction. After setting the parameter of motor (power, current, voltage), firstly
to jog run, and the direction of observation to ensure the right direction is that the elevator
goes up. If the direction is reserve, change the sequence of 3 phase AC input.
8.
Brake control and main contactor control
Function
code
Name
Description
Range
Modify
Factory
setting
P06.01
Y output
selection
0:Without output
1:Running
0~30
○
5
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...