Goodrive200L
inverters Communication protocol
149
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
06H
High bit of writing data address
00H
Low bit of writing data address
04H
High bit of data content
13H
Low bit of data content
88H
CRC CHK low bit
C5H
CRC CHK high bit
6EH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Note:
section 10.2 and 10.3 mainly describe the command format, and the detailed
application will be mentioned in 10.8 with examples.
9.4.3 Command code 08H for diagnosis
Meaning of sub-function codes
Sub-function Code
Description
0000
Return to inquire information data
For example: The inquiry information string is same as the response information string when
the loop detection to address 01H of driver is carried out.
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The RTU response command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...