![INVT GD200L-004G-4 Скачать руководство пользователя страница 88](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737088.webp)
Goodrive200L
inverters Function parameters
83
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
gain at low
frequency
(Kp)
P09.15
PID
command of
ACC/DEC
time
0.0~1000.0s
0.0s
○
P09.16
PID output
filter time
0.000~10.000s
0.000s
○
P10 Group Simple PLC and multi-step speed control
P10.00 Simple PLC
0: Stop after running once. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the inverter will keep the running
frequency and direction of the last run.
2: Cycle running. The inverter will keep on
running until receiving a stop command and then,
the system will stop.
0
○
P10.01
Simple PLC
memory
0: Power loss without memory
1:Power loss memory
;
PLC record the running
step and frequency when power loss.
0
○
P10.02
Multi-step
speed 0
100.0% of the frequency setting corresponds to
the Max. frequency P00.03.
When selecting simple PLC running, set
P10.02~P10.33 to define the running frequency
and direction of all steps.
Note:
The symbol of multi-step determines the
running direction of simple PLC. The negative
value means reverse rotation.
Multi-step speeds are in the range of --f
max
~f
max
and it can be set continuously.
Goodrive200L series inverters can set 16 steps
0.0 HZ
○
P10.03
The running
time of step
0
0.0s
○
P10.04
Multi-step
speed 1
5.0 HZ
○
P10.05
The running
time of step 1
0.0s
○
P10.06
Multi-step
speed 2
15.0 HZ
○
P10.07
The running
time of step 2
0.0s
○
P10.08
Multi-step
speed 3
50.0 HZ
○
P10.09
The running
time of step 3
0.0s
○
P10.10
Multi-step
0.0 HZ
○
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...