Goodrive200L
inverters Function parameters
96
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
counting
P20.13
Pg1 Pulse
counting
down low
0~65535
0
●
P24 Group Water supply
P24.00
Water
supply
selection
0: Disabled
1: Enabled
0
◎
P24.01
Press
feedback
source
0: AI1 setting value (The inverter(
≤
15kW) can be
set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5 kW)
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
0
○
P24.02
Hibernation
check
0: Hibernate as the setting frequency
﹤
P24.03
1: Hibernate as the feedback pressure
﹥
P24.04
0
◎
P24.03
Starting
frequency of
the
hibernation
0.00~P0.03(the Max. frequency)
10.00
Hz
○
P24.04
Starting
pressure of
hibernation
0.00~100.0%
50.0%
○
P24.05
Hibernation
delay time
0.0~3600.0s
5.0s
○
P24.06
Hibernation
awake
0: Awake as the setting frequency
﹥
P24.07
1: Awake as the feedback pressure
﹤
P24.08
0
◎
P24.07
Awake
frequency
0.00~P0.03(the Max. frequency)
20.00
Hz
○
P24.08
Setting value
of hibernation
awake
0.00~100.0%
10.0%
○
P24.09
Mini
hibernation
time
0.0~3600.0s
5.0s
○
P24.10
Valid
P24.10~P24.12 can make three motors to form a
0
○
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...