Goodrive200L
inverters Appendix C
178
is calculated at 100% of the braking torque, 10%, 50% and 80%of the braking usage ratio.
The user can select according to the actual working.
Refer to the operation instructions of braking units when using external units for right setting
of voltage degree. Otherwise normal operation of the inverter may be impacted.
The inverter
Braking unit
type
100% of
braking
rate
(Ω)
The consumed power of the
braking resistor
Mini
Braking
Resistor
(Ω)
10%
braking
50%
braking
80%
braking
GD200L -0R7G-4
Internal braking
unit
653
0.1
0.6
0.9
240
GD200L -1R5G-4
326
0.23
1.1
1.8
170
GD200L -2R2G-4
222
0.33
1.7
2.6
130
GD200L-004G/5R5P-4
122
0.6
3
4.8
80
GD200L-5R5G/7R5P-4
89
0.75
4.1
6.6
60
GD200L -7R5G/011P-4
65
1.1
5.6
9
47
GD200L -011G/015P-4
44
1.7
8.3
13.2
31
GD200L -015G/018P-4
32
2
11
18
23
GD200L -018G/022P-4
27
3
14
22
19
GD200L -022G/030P-4
22
3
17
26
17
GD200L -030G/037P-4
16
5
23
36
17
GD200L -037G/045P-4 DBU100H-060-4
13
6
28
44
11.7
GD200L -045G/055P-4
DBU100H-110-4
10
7
34
54
6.4
GD200L -055G/075P-4
8
8
41
66
GD200L -075G/090P-4
6.5
11
56
90
GD200L -090G/110P-4
DBU100H-160-4
5.4
14
68
108
4.4
GD200L -110G/132P-4
4.5
17
83
132
GD200L -132G/160P-4 DBU100H-220-4
3.7
20
99
158
3.2
GD200L -160G/185P-4
DBU100H-320-4
3.1
24
120
192
2.2
GD200L -185G/200P-4
2.8
28
139
222
GD200L -200G/220P-4
2.5
30
150
240
GD200L -220G/250P-4
DBU100H-400-4
2.2
33
165
264
1.8
GD200L -250G/280P-4
2.0
38
188
300
GD200L -280G/315P-4
Two
DBU100H-320-4
3.6*2
21*2
105*2
168*2
2.2*2
GD200L -315G/350P-4
3.2*2
24*2
118*2
189*2
GD200L -350G/400P-4
2.8*2
27*2
132*2
210*2
GD200L -400G-4
2.4*2
30*2
150*2
240*2
GD200L -500G-4
Two
DBU100H-400-4
2*2
38*2
186*2
300*2
1.8*2
Never use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are
not able to handle the overcurrent caused by the low resistance.
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...