6.1 Parameter
B6-57
ME0384-4A
St
ar
tu
p
Se
ct
io
n
[Home position adjustment (Parameter No. 4)]
No.
Name
Unit
Input range
Default initial value setting
4
Home position adjustment
mm
0 to 9999.99
According to ELECYLINDER
specifications
●
Setting is established at delivery based on the ELECYLINDER specifications. It is not
necessary to adjust the setting in normal use.
●
Sets the distance between the home side mechanical stopper and the home position.
●
The minimum setting unit is 0.01mm.
●
Adjustment with this parameter is possible in the following situations.
(1) To match the ELECYLINDER home position and the mechanical home position after assembly into
equipment.
(2) To adjust the new home position upon reversing the default home return direction after purchase.
(3) To eliminate a slight deviation from the previous home position generated after replacing the
ELECYLINDER.
If [Parameter No.4] is [0.30mm],
the relationship between mechanical stopper and home position is as follows.
Caution
●
If adjusting Parameter No.4, simultaneously adjust Parameter No.1.
Operation range adjustment with parameter No.1 uses the home position as the datum.
●
Do not set Parameter No.4 to a value smaller than the default setting at shipping.
This may result in abnormal home return operation, alarm triggering or abnormal
operation. If the value must be set small, please contact IAI.
●
After changing this parameter, always perform home return reset (absolute reset).
Configuration example
0.30mm
0.30mm
80.00mm
(Stroke to be used)
Parameter No.4: 0.30mm
Home position
Elecylinder only
Содержание Rcon
Страница 12: ...ME0384 4A ...
Страница 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Страница 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Страница 45: ...ME0384 4A ...
Страница 291: ...ME0384 4A ...
Страница 323: ...ME0384 4A ...
Страница 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Страница 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Страница 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Страница 606: ...1 5 Predictive Maintenance Function C1 17 ME0384 4A Maintenance Section Chapter 1 Maintenance and Inspection ...
Страница 644: ...2 5 Causes and countermeasures for ELECYLINDER alarms C2 37 ME0384 4A Maintenance Section Chapter 2 Troubleshooting ...
Страница 662: ...1 1 Conforming to safety category D1 17 ME0384 4A Appendix Chapter 1 Conforming to Safety Category ...
Страница 837: ......
Страница 838: ......