3.8 I/O Signals
A3-91
ME0384-4A
Spec
ifi
cat
ion
s
Sec
tion
Chapt
er 3 G
at
eway
Uni
t
Function of I/O signals
I/O signals are prepared for each axis No.
ON means that the corresponding bit is "1" and OFF means the corresponding bit is "0".
Refer to "Features of Input and Output Signals for EC Connection Unit (Pg. A3-114)" for the EC
connection unit.
[1] Controller ready (CRDY) PLC input signal
Operation mode Direct numerical control Simple direct Positioner 1 Positioner 2 Positioner 3 Positioner 5
○
: Y
×
: N
○
○
○
○
×
○
Regardless of the alarm status, servo status and the like, when the power is turned ON, driver
unit initialization normally completes, and control is enabled, it turns ON.
It will turn ON even during alarm status if the driver unit is enabled.
[2] Emergency stop (EMGS) PLC input signal
Operation mode Direct numerical control Simple direct Positioner 1 Positioner 2 Positioner 3 Positioner 5
○
: Y
×
: N
○
○
○
○
○
○
This signal turns ON when the condition gets to the motor drive cutoff status.
(1) STOP Signal Input: OFF
(2) MP 24V: OFF
(3) MPI_I or MPI_II Signal: OFF (EMGS: ON only on axis with motor drive source cut off)
(4) 200V Power Supply input
:
OFF
It turns OFF once the motor drive cutoff status gets cancelled.
Also, the SYS of the driver unit LED lights up in red.
On the host device such as a PLC, apply appropriate safety measures such as interlocking
using this signal.
It is not an output signal caused by the driver unit alarm.
[3] Alarm (ALM) PLC input signal
Operation mode Direct numerical control Simple direct Positioner 1 Positioner 2 Positioner 3 Positioner 5
○
: Y
×
: N
○
○
○
○
○
○
It is a signal that turns OFF when it is normal and turns ON when an alarm of operation cancel
level or higher is generated.
This signal turns OFF when the reset signal RES is turned ON while the operation cancel level
alarm is generated. (For a cold start level alarm, the power must be turned on again.)
Also, the SYS of the driver unit LED lights up in red.
For details on alarms, refer to "Maintenance Section Chapter 2, 2.4 Simple Absolute Unit Alarm
Causes and Countermeasures".
Содержание Rcon
Страница 12: ...ME0384 4A ...
Страница 32: ...Actuator Coordinate System Intro 20 ME0384 4A ...
Страница 42: ...1 3 General Specifications A1 9 ME0384 4A Specifications Section Chapter 1 RCON Overview ...
Страница 45: ...ME0384 4A ...
Страница 291: ...ME0384 4A ...
Страница 323: ...ME0384 4A ...
Страница 384: ...1 3 Startup Procedure B1 9 ME0384 4A Startup Section Chapter 1 Overview ...
Страница 420: ...3 6 Precautions B3 15 ME0384 4A Startup Section Chapter 3 Absolute Reset ...
Страница 588: ...6 2 Various Functions B6 81 ME0384 4A Startup Section ...
Страница 606: ...1 5 Predictive Maintenance Function C1 17 ME0384 4A Maintenance Section Chapter 1 Maintenance and Inspection ...
Страница 644: ...2 5 Causes and countermeasures for ELECYLINDER alarms C2 37 ME0384 4A Maintenance Section Chapter 2 Troubleshooting ...
Страница 662: ...1 1 Conforming to safety category D1 17 ME0384 4A Appendix Chapter 1 Conforming to Safety Category ...
Страница 837: ......
Страница 838: ......