Space and airflow requirements
Space and airflow requirements
CAUTION:
CAUTION: In high-density configurations, the HPE 11000 G2 Series Rack Airflow Optimization Kit (BW930A) must be
installed to prevent airflow from the rear of the rack to the front the rack through gaps in the rack frame.
To enable servicing and ensure adequate airflow, observe the following spatial requirements when deciding where to install a Hewlett
Packard Enterprise-branded, Compaq-branded, Telco, or third-party rack:
Leave a minimum clearance of 63.5 cm (25.0 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30.0 in) in back of the rack.
Leave a minimum clearance of 121.9 cm (48.0 in) from the back of the rack to the rear of another rack or row of racks.
Compute modules draw cool air in through the front and expel warm air through the rear of the frame. Therefore, the front of the frame
must be adequately ventilated to enable ambient room air to enter the frame, and the rear of the frame must be adequately ventilated to
enable the warm air to escape from the frame.
Hewlett Packard Enterprise Advanced Series Racks, Hewlett Packard Enterprise Series Racks, and Hewlett Packard Enterprise Standard
Series Racks provide proper compute module cooling through flow-through perforations in the front and rear doors that provide 65
percent open area for ventilation.
If the front of the rack is not filled with components, the remaining gaps between the components can cause changes in the airflow, which
can adversely affect cooling within the rack. Cover these gaps with blanking panels.
IMPORTANT:
IMPORTANT: Do not block the ventilation openings.
CAUTION:
CAUTION: Always use blanking panels to fill empty vertical spaces in the rack. This arrangement ensures proper airflow.
Using a rack without blanking panels results in improper cooling that can lead to thermal damage.
Space and airflow requirements
15
Содержание HPE Synergy 12000 Frame
Страница 7: ...Planning the installation Planning the installation 7 ...
Страница 23: ...Component and LED identification Component and LED identification 23 ...
Страница 25: ...Information pull tabs 25 ...
Страница 29: ...Figure 5 Optional horizontal half shelf Device bay partitions 29 ...
Страница 33: ...Appliance bay numbering Appliance bay numbering 33 ...
Страница 67: ...Installation Installation 67 ...
Страница 85: ...Installing a device bay shelf 85 ...
Страница 98: ...Installing drives in the storage module 98 ...
Страница 101: ...Installing interconnect modules 101 ...
Страница 119: ...Installing the DC power grounding kit with bracket 119 ...
Страница 122: ...Configuring HPE Synergy Configuring HPE Synergy 122 ...
Страница 124: ...HPE Synergy Console connections HPE Synergy Console connections 124 ...
Страница 149: ...Troubleshooting Troubleshooting 149 ...
Страница 157: ...Shift Insert Paste selected text Keyboard shortcut Action HPE Synergy Console icons 157 ...
Страница 175: ...Support and other resources Support and other resources 175 ...