Power supply configurations
Power supply configurations
Sufficient power supplies must be installed to support the installed devices and interconnect modules. Power estimates for HPE Synergy
can be provided using either the HPE Synergy Planning Tool or the HPE Power Advisor. For more information about the HPE Power
Advisor or the HPE Synergy Planning Tool, see the Data Center Infrastructure Advisor page (https://dcia.itcs.hpe.com/
The number of supported power supplies in the frame range from a minimum of two to a maximum of six power supplies. There are no
power supply bay placement restrictions of power supplies in the frame. However, for best cooling and power distribution, Hewlett
Packard Enterprise recommends the following best practice for power supply usage.
NOTE:
NOTE: The default power mode is Redundant power feed mode.
Number of power
Number of power
supplies
supplies
Power modes
Power modes
Power supply bay (power feed)
Power supply bay (power feed)
1
Not supported
—
2
Redundant power supply mode
Redundant power feed mode
1(A) and 3(A)
1(A) and 3(B)
Redundant power supply mode
1(A), 3(A), and 5(A)
4
Redundant power supply mode
Redundant power feed mode
1(A), 3(A), 4(A), and 6(A)
1(A), 3(B), 4(A), and 6(B)
Redundant power supply mode
1(A), 2(A), 3(A), 4(A), and 6(A)
6
Redundant power supply mode
Redundant power feed mode
1(A), 2(A), 3(A), 4(A), 5(A), and 6(A)
1(A), 2(A), 3(B), 4(A), 5(B), and 6(B)
If an odd number of power supplies are installed in a frame that is configured for redundant power feed mode, all power supplies are
providing power to the frame, but the capacity of the odd power supply is not used to determine the overall power capacity of the
frame.
To enhance cooling, populate all power supply bays with either a power supply blank or a power supply.
Power supply configuration recommendations for the frame do not depend on the type of power supply being used. However, all power
supplies must be of the same type. Mixed-type power supply configurations are not supported.
1
Power supply configurations
112
Содержание HPE Synergy 12000 Frame
Страница 7: ...Planning the installation Planning the installation 7 ...
Страница 23: ...Component and LED identification Component and LED identification 23 ...
Страница 25: ...Information pull tabs 25 ...
Страница 29: ...Figure 5 Optional horizontal half shelf Device bay partitions 29 ...
Страница 33: ...Appliance bay numbering Appliance bay numbering 33 ...
Страница 67: ...Installation Installation 67 ...
Страница 85: ...Installing a device bay shelf 85 ...
Страница 98: ...Installing drives in the storage module 98 ...
Страница 101: ...Installing interconnect modules 101 ...
Страница 119: ...Installing the DC power grounding kit with bracket 119 ...
Страница 122: ...Configuring HPE Synergy Configuring HPE Synergy 122 ...
Страница 124: ...HPE Synergy Console connections HPE Synergy Console connections 124 ...
Страница 149: ...Troubleshooting Troubleshooting 149 ...
Страница 157: ...Shift Insert Paste selected text Keyboard shortcut Action HPE Synergy Console icons 157 ...
Страница 175: ...Support and other resources Support and other resources 175 ...