E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
13
Optional Modules
System Overview
1.4 Optional Modules
The following subsections list the optional sub-assemblies and features.
1.4.1 Addressable Switch Sub-Assembly (ASM-16)
The ASM-16 is a configurable switch input sub-assembly with 16 switches and 48 status LEDs. It
may be remotely located via the RS-485 serial interface. Each switch address is fully software
programmable to serve as:
•
A System Control Switch; Reset, Silence, Alarm and Trouble Acknowledge, etc.
•
A Voice Evacuation Speaker
Circuit control switch
•
A Fire Fighter Communication Circuit control switch
•
An Auxiliary Control Circuit switch
•
A status indicating LED,
red, green, and yellow
•
A status indicating LED, labeled to display, “Command Center in Control”
1.4.2 Digital Alarm Communicator Transmitter (DACT-E3)
The DACT-E3 provides an integral, remote Digital Alarm Communicator Transmitter (DACT). It
is fully programmable from the keypad, which is compatible with Digital Alarm Communicator
Receivers (DACRs) that can receive the following formats:
•
SIA DC8
•
SIA DCS20
•
Ademco Contact ID
•
3+1 1400 Hz
•
3+1 2300 Hz
•
4+2 1400 Hz
•
4+2 2300 Hz
The DACT-E3 can be remotely located via the local RS-485 serial interface.
1.4.3 Repeater (RPT-E3)
The RPT-E3 sub-assembly provides a remote interface between the ILI-MB-E3, ILI95-MB-E3,
and/or ANX, and the Broadband Network. The unit can be used with unshielded, twisted-pair wire
or fiber-optic cable as the Model (RPT-E3-FO). The Model (RPT-E3-UTP) is used with only
twisted-pair.
1.4.4 Intelligent Loop Interface - Slave Board (ILI-S-E3)
These sub-assemblies provide two (2), additional signaling line circuits. The units are physically
identical to the ILI-MB-E3 except some components are omitted. Each unit occupies one node on
the Broadband network. The following sensors and modules are used with each unit.
•
The ILI-S-E3 accommodat
es the ASD/ATD Series sensors and AMM/MMI/AOM/MMO
Series modules.
For a comprehensive list, refer to the Compatibility Addendum to Gamewell-FCI Manuals,
P/N 9000-0427.
•
Audible Sounder
An Alarm/Trouble/Supervisory sounder is located on the ILI-S-E3.
1.4.5 Intelligent Loop Interface XP95 - Slave Board (ILI95-S-E3)
These sub-assemblies provide two (2), additional signaling line circuits. The units are physically
identical to the ILI95-MB-E3 except some components are omitted. Each unit occupies one node
on the Broadband network. The following sensors and modules are used with each unit.
•
The ILI95-S-E3 accommodates the Apo
llo Series of sensors and modules.
For a comprehensive list, refer to the Compatibility Addendum to Gamewell-FCI Manuals,
P/N 9000-0427.
•
Audible Sounder
An Alarm/Trouble/Supervisory sounder is located on the ILI95-S-E3.
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...