E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
165
LCD-E3 Panel Display Connections
E3 Series System Connections
3.13.3 LCD-E3 Wiring Connections
Table 3.13.3.1 lists the field wiring connections for the LCD-E3.
Designation
Description
Comments
TB1-1
+24
+24V in from ILI-MB-E3 or ILI95-MB-E3 TB3-6
non-resettable B+
TB1-2
GND
ILI-MB-E3 or ILI95-MB-E3 TB3-7
TB1-3
RS-485A
RS-485A output from ILI-MB-E3 or ILI95-MB-E3
TB1-4
RS-485B
RS-485B output from ILI-MB-E3 or ILI95-MB-E3
TB1-5
RS-485A
RS-485A input from ILI-MB-E3 or ILI95-MB-E3
TB1-6
RS-485B
RS-485B input from ILI-MB-E3 or ILI95-MB-E3
TB1-7
GND
Connect to earth ground
TB1-8
Not used
J1
Local RS-485
Alternate RS-485 connection
J2
Keypad
To keypad
J3
Display
To display
J4
Factory use
W1
RS-485 Termination
W1 should be CLOSED if it is the first or last device
on the RS-485 bus.
Otherwise, W1 should be OPEN.
W2
Keypad
Keypad
IN = Disabling
OUT = Enabling
Table 3.13.3.1 LCD-E3 Wiring Connections
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...