182
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
Power-Limited
– Non Power-Limited Wiring
E3 Series Control Panel Circuit Wiring Requirements
8.1 E3 Series Control Panel Circuit Wiring Requirements
Table 8.1.1 provides the circuit wiring requirements for the E3 Series control panel.
Circuit Type Circuit Function
Wire Requirements
Distance
(feet/meters)
Typical Wire Type*
SLC
(power-limited)
Connects to
intelligent and
addressable
modules.
Twisted-unshielded pair, 12 to 18 AWG
(3.1 to 0.78 mm
2
) 40 Ohms maximum
per length of Style 6 & 7 loops. 40
Ohms combined-branch circuits
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
10,000 ft. (3,000 m)
12 AWG (3.1 mm
2
)
8,000 ft. (2,400 m)
14 AWG (2.00 mm
2
)
4,875 ft. (1,450 m)
16 AWG (1.30 mm
2
)
3,225 ft. (980 m)
18 AWG (0.78 mm
2
)
Or
Shielded wire, in conduit or outside of
conduit or MC cable.
MC cable with 3 conductor twisted.
1,000 ft. (304.8 m)
12 to 18 AWG
(3.1 to 0.78 mm
2
)
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
EIA-485
(power-limited)
Connects to
LCD-E3, ASM-16,
and ANU-48
modules
Twisted-unshielded pair with a
characteristic impedance of 120
Ohms. 18 AWG (0.78 mm
2
) minimum.
3,000 ft .(maximum) 16 AWG (1.30 mm
2
)
EIA-232
(power-limited)
Connects to
Printers, CRT,
E3 or PC.
Twisted-unshielded pair. 18 AWG
(0.78 mm
2
) minimum
50/15.24
(without modem)
16 AWG (1.30 mm
2
)
NAC
Notification
Appliance
Circuit
E3
(power-limited)
12-18 AWG (3.1 to 0.78 mm
2
). At
alarm current level, no more than a 1.2
V drop at the end of the circuit, or sized
to provide the minimum rated
operating voltage of the appliances
used.
To meet 1.2 V drop, or
sized to provide the
minimum rated
operating voltage of
the appliances used.
12 to 18 AWG
(3.1 to 0.78 mm
2
)
24 VDC Power
Runs
(power-limited)
To Transmitter
Annunciator
12-18 AWG (3.1 to 0.78 mm
2
). Size
wire so that no more than 1.2 V drop
across wire run from supply source to
end of any branch.
To meet 1.2 volt drop 12 to 18 AWG
(3.1 to 0.78 mm
2
)
CHG-120
External battery
charger
12 AWG (3.1 mm
2
) in conduit
20/6.1 (maximum)
12 AWG (3.1 mm
2
)
ARCNET
(power-limited)
Provides interface
between network
nodes.
ARCNET should
be installed in a
separate conduit.
Twisted-unshielded pair, low
capacitance 18 AWG
3,000 ft. (.914 m)
18 AWG (3.1 mm
2
)
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL
1459.
Table 8.1.1 E3 Series Control Panel Wiring Requirements
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...