E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
System Overview
Specifications
1.5.10 Battery Connection (PM-9/PM-9G)
•
Supervised
•
24 VDC nominal
•
Maximum battery size 55 AH (with
an external battery cabinet)
•
1.7 Amp maximum battery charge current
•
Non power-limited
1.5.11 City Master Box Output (ILI-MB-E3 or ILI95-MB-E3)
1.5.12 Remote Signaling Output (Polarity Reversal)
(ILI-MB-E3 or ILI95-MB-E3)
1.5.13 Releasing Service (ILI-MB-E3 or ILI95-MB-E3)
Refer to the Compatibility Addendum to Gamewell-FCI Manuals, P/N 9000-0427, Section 3 for a
list of UL Listed, compatible releasing solenoids.
Voltage:
24 VDC (Nominal) FWR
Supervisory Current:
.0018 amp
Alarm Current:
.510 amp (max.)
Box Trip Coil Resistance: 14.5 Ohms (max.)
Line Resistance:
35 Ohms (max.)
Supervised against Opens and Grounds
Non Power-limited
Voltage:
24 VDC (nominal) FWR
Supervisory Current:
.012 amp
Alarm Current:
.012 amp
Line Resistance:
2 ohms (max.)
Supervised against Opens and Grounds
Non Power-limited
Voltage:
24 VDC (Nominal) FWR
Supervisory Current:
.0005 amp
Alarm Current:
.700 amp (max.)
Line Resistance:
2 Ohms (max.)
Supervised against Opens and Grounds
Non Power-limited
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...