154
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Repeater (RPT-E3) Connections
3.11.5 Repeater-E3 Wiring Connections
Table 3.11.5.1 lists the field wiring connections for the RPT-E3.
Designation
Description
Comments
TB1-1
ARCNET PORT 1A
Broadband Network (See Note 1)
TB1-2
ARCNET PORT 1B Broadband Network (See Note 1)
TB1-3
ARCNET PORT 2A
Broadband Network (See Note 1)
TB1-4
ARCNET PORT 2B
Broadband Network (See Note 1)
TB2
Earth Ground
Local Differential ARCNET (See Note 2)
TB3-1
COM A IN
Local Differential ARCNET (See Note 3)
TB3-2
COM B IN
Local Differential ARCNET (See Note 3)
TB3-3
COM A OUT
Local Differential ARCNET. Connect to NGA TB1-3. (See Note 3)
TB3-4
COM B OUT
Local Differential ARCNET. Connect to NGA TB1-4. (See Note 3)
TB4-1
+ 24V IN
Do not use, if J10 is used.
(+24 VDC IN from TB3-6 ILI-MB-E3/ILI95-MB-E3/ANX)
TB4-2
Common
– IN
Do not use, if J10 is used.
(-GND IN from TB3-7 ILI-MB-E3/ILI95-MB-E3/ANX)
TB4-3
+ 24 V OUT
Do not use, if J10 is used.
TB4-4
Common
– OUT
Do not use, if J10 is used.
J10
ARCNET
Connector to ILI-MB-E3 or ILI95-MB-E3 (See Note 4)
U5
Fiber Port 2 IN
(See Note 5)
U7
Fiber Port 2 OUT
(See Note 5)
U4
Fiber Port 1 IN
(See Note 5)
U6
Fiber Port 1 OUT
(See Note 5)
J1
ARCNET Term
Short when using the Local Differential ARCNET wiring to Terminal TB3. This
is the last device on the local net.
Note: If the first and last devices are SHORT, then the device between the two
must be OPEN. If the ILI-E3, ILI95-E3 Series or ANX is the first device and
the NGA is the last device, then the RPT-E3 or J1 would be OPEN.
J2
GFI
Short to enable Ground Fault Detection on the ARCNET Network when using
copper wiring.
J3
GND FLT
Short to enable Ground Fault Detection when remotely connected to a Listed
power source that does not provide earth detection.
OPEN when connected to the DC power supplied from an ILI-MB-E3,
ILI95-MB-E3, ANX, PM-9/PM-9G or INI-7100.
J4
Transmitter Light
Output Control
Comm port 1 fiber-optic transmitter drive current
Jumper contributes to drive current when SHORT.
Contributes 12.5% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 SHORT - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
J5
Transmitter Light
Output Control
Comm port 1 fiber-optic transmitter drive current
Jumper contributes to drive current when SHORT.
Contributes 25% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 SHORT - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
Table 3.11.5.1 Repeater-E3 Wiring Connections
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...