130
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
PM-9/PM-9G Power Supply Connections
3.8.2 PM-9/PM-9GBattery Connections
•
Two (2), twelve volt batteries are co
nnected in series to the PM-9/PM-9G.
•
TB3-1 is positive. (For PM-9, see Table 3.8.5.1 and for PM-9G, see Table 3.8.8.1)
•
TB3-2 is negative. (For PM-9, see Table 3.8.5.1 and for PM-9G, see Table 3.8.8.1)
•
14 AWG wire minimum
•
Observe polarity
See Table 3.15.1 for the Battery Calculations.
3.8.3 PM-9 and PM-9G Specifications
3.8.3.1 PM-9/PM-9G
The following list the electrical specifications for the PM-9 and PM-9G.
Specifications
PM-9
PM-9G
Input Voltage:
120 VAC, 60 Hz
240VAC @ 50/60 Hz
Input Current:
4.6 amps max. @ 120 VAC 60 Hz 2.4 amps max.
Output Voltage:
24 VDC FWR
24 VDC FWR
Output Current:
9 amperes Alarm max. continuous 9 amperes Alarm max. continuous
Output Current:
5 amperes max. continuous
Standby (when the PM-9 is used
with the ILI-E3 or the ILI95-E3
Series) (See Note 1)
5 amperes max. continuous Standby
(when the PM-9G is used with the
ILI-E3 or the ILI95-E3 Series)
(See Note 1)
Output Current:
4 amperes max. continuous
Standby (when the PM-9 is used
with any AM-50 Series amplifier)
(See Note 2)
4 amperes max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier)
(See Note 2)
Operating Temperature: 32
° to 120° F (0° to 49° C)
32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing at 90
° F
(32
° C)
0 to 93%, non-condensing at 90
° F
(32
° C)
Supervised
Non Power-Limited
NOTE 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 Standby
Battery Calculations in this Manual.
NOTE 2: Continuous standby loads in excess of .560 Amps up to 4 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 Standby
Battery Calculations in this Manual.
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...