116
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Addressable Node Expander (ANX) Connections
3.7.3 ANX Wiring Requirements
Table 3.7.3.1 lists the wiring requirements for the ANX-SR, ANX-MR-FO and ANX-MR-UTP
sub-assemblies.
3.7.4 FocalPoint Gateway-3 Wiring
The FocalPoint Gateway panel wiring information and diagrams are included in the FocalPoint
Gateway-3 Installation & Operation Manual. For information on the wiring and operation of the
FocalPoint Gateway-3 panel, refer to the FocalPoint Gateway-3 Installation & Operation Manual,
P/N 53553.
3.7.5 License
3.7.5.1 From uIP
©
uIP
©
is an open source software, licensed under the following BSD-style license:
Copyright (c) 2001-2006, Adam Dunkels and the Swedish Institute of Computer Science All rights
reserved.
Circuit Type
Circuit Function Wire Requirements
Distance
Wire Type*
EIA-232
(power-limited)
Connects to Printers,
CRT, or PC.
Twisted-unshielded
pair. 18 AWG
(0.78 mm
2
) minimum
50/15.24
(without modem)
16 AWG (1.30 mm
2
)
ARCNET
(power-limited)
Provides the interface
between network
nodes. ARCNET
should be installed in
a separate conduit.
Twisted-unshielded
pair low capacitance
18 AWG
3,000 ft. (.914 m)
18 AWG (3.1 mm
2
)
Ethernet
(See Note 2)
Data Communications CAT5
(Crossover or Straight-
through)
300 ft. (100 m)
(10/100 Ethernet)
CAT5
NOTE 1: The lightning arresters are required on circuits extending between buildings; 999 meter length maximum
to meet UL 1459.
NOTE 2: The PNET1GB Ethernet circuit protector is required for permanent connections (for example, FocalPoint).
Table 3.7.3.1 ANX Wiring Requirements
NOTE: SOFTWARE WARRANTY DISCLAIMER
THIS SOFTWARE IS PROVIDED BY THE AUTHOR
‘AS IS’ AND ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT
SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY,
OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION). HOWEVER, CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN
ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF
SUCH DAMAGE.
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...