4.3 Switches (LCD-E3)
Figure 4.3.1 illustrates the LCD-E3 switches. Table 4.3.1 lists the LCD-E3 switches and a
description.
Figure 4.3.1 LCD-E3 Switches
Designation
Comments
Alarm Acknowledge
Silences the panel audible sounder. This must be pressed once for each
Alarm condition present in the system.
Trouble Acknowledge
Silences the panel audible sounder. This must be pressed once for each
Trouble or Supervisory condition present in the system.
Signal Silence
Press once and any outputs programmed as silenceable will be
deactivated. (All applicable silence LEDs will light). A second activation
will re-activate the previously silenced outputs. This switch only
functions if an Alarm or Supervisory condition exists in the system.
Lamp Test/Reset
Press momentarily and all LEDs (including all elements in the display)
will light momentarily. Press and hold to reset the system.
Menu/Back
Used to access certain system functions, e.g. Walk Test. The display will
prompt the operator as to which function applies.
“Menu” is pressed to initially put the E3 Series
®
into Menu Mode. The
“Back” function will step
the operator out of the menu mode one element
at a time.
BKSP/Edit
Used in menu operations. The display will prompt the operator as to
which function applies.
OK
Accepts any changes made in the Menu field.
Numeric Keys
These 12 keys allow the user to choose a specific point address by
using the numbers for point sensitivity reading, disabling an address,
etc.
Table 4.3.1 Switches
AC POWER
ON
POWER
FAULT
GROUND
FAULT
ALARM
SYSTEM
TROUBLE
SUPERVISORY SYSTEM
SILENCED
ALARM
ACKNOWLEDGE
TROUBLE
ACKNOWLEDGE
SIGNAL
SILENCE
SYSTEM RESET/
LAMP TEST
MENU
BACKSPACE/
EDIT
OK/
ENTER
ABC
2
MNO
6
.
-QZ
1
DEF
3
GHI
4
JKL
5
PRS
7
TUV
8
WXY
9
<
>
0
_
,
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...