144
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Digital Alarm Communicator Transmitter (DACT-E3) Connections
3.10 Digital Alarm Communicator Transmitter (DACT-E3)
Connections
The DACT-E3 digital communicator transmitter is an optional sub-assembly that features
numerous formats for the communication to a central station. It provides the following functions:
•
Line seizure - takes control of the phone lines,
disconnecting any premises phones using the
same lines
•
Off/On-Hook - perform on and off-hook status to phone lines
•
Listen for dial tone - 440 Hz tone typical in most networks
•
Dialing the Central Station phone number - programmable
•
Discern proper Central Station “ACK” and “Kiss-off” tone
•
Transmit data to the Central Station
•
Verify that data has been
accepted by the Central Station
•
Hang-up and release phone lines
•
Communicate in a variety of formats
•
Remote via the RS-4
85 serial interface
3.10.1 Central Station Reporting
UL Listed receivers compatible with the E3 Series
®
are listed in Table 3.10.1.1.
Manufacturer
Receiver Model
Formats
Silent Knight
Model 9000.
SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
Silent Knight
Model 9800/9500 SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
Contact ID
Ademco
Model 685
3/1 14
3/1 23
Sur-Guard
(Version. 1.64 or higher)
SG-MLR2-DG
SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
Contact ID
Osborne Hoffman
Quickalert
SIA-8
SIA-20
If you are using the Model 9000 and the message,
“HELP,” appears on the printer after attempting
to download, the 9000 software must be upgraded.
The Model 9000 must have the Model 9307 software package, Revision 900501 or later, to print the
PROGRAMMING PASS and PROGRAMMING FAIL messages.
Table 3.10.1.1 UL Listed Receivers Compatible with the E3 Series
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...