E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
149
Digital Alarm Communicator Transmitter (DACT-E3) Connections
E3 Series System Connections
3.10.5.1 Reporting Codes for Non-SLC-Device Events
For events that do not originate on SLC devices, the DACT-E3 reports extended codes in the range
900-999. These codes are not user-configurable. Figure 3.10.5.1.1 lists the extended codes.
Code
Event
Comment
000
Phone Line Test
Automatic DACT test OK.
001 - 899
SLC Device Codes
User-defined in device configuration
900
Reserved
901
SLC 1
Loop Break, Short, or Disconnect
902
SLC 2
Loop Break, Short, or Disconnect
903
NAC 1
Fault, Short, or Disconnect
904
NAC 2
Fault, Short, or Disconnect
905
Municipal Circuit
Master Box Trouble
906
Aux Power Fault
Resettable or Non-Resettable B+ Fault
907
Municipal Circuit Supervision
908
Positive Ground Fault
909
Negative Ground Fault
910
RS-232 Supervision Fault
911
Annunciator Fault
912
PM-9/PM-9G Supervision
Fault
913
Battery Low
914
Battery Fault
915
AC Fault
916
DC Fault
917
Reserved
918
Battery Charger Fault
919 - 924
Reserved
925
DACT Account 1 Fault
926
DACT Missing
927
DACT Report Timeout
928
DACT Account 2 Fault
929
DACT Line 1 Fault
930
DACT Line 2 Fault
931
INI Communication Fault
932
INI Node Number Fault
Issued if node address DIP switches do not match the node number
in the node
’s configuration.
933
Net Port 1
934
Net Port 2
935 - 950
Reserved
951 - 981
Cross Zone 1 - 31
Cross Zone 31 (981) is used to report Group Cross Zone Events.
982
Node Missing Faults
Node not reported
983
Node Extra Faults
Node not reported, reports only when Extra Node enabled
984
LCD Display Faults
Address not reported
985
ASM/ANU Faults
Address not reported
986
External Faults
e.g. INI-VG troubles that have no ILI equivalent
987 - 999
Reserved
991
Test with Exception
Automatic DACT test OK, but Trouble condition present in the system.
992 - 999
Reserved
Table 3.10.5.1.1 Non-SLC Device Events Reporting Codes
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...