E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
125
Addressable Node Expander (ANX) Connections
E3 Series System Connections
3.7.8.1 ANX-MR-FO Wiring Connections
Table 3.7.8.1.1 lists the wiring connections for the ANX-MR-FO.
Designation
Description
Comments
TB1-1
+24V
+24 VDC Input from the PM-9/PM-9G TB4-1
TB1-2
GND
Common negative from the PM-9/PM-9G TB4-2
TB1-3
+24V
TB1-4
GND
TB2-1
COM A IN
Local Differential ARCNET
TB2-2
COM B IN
Local Differential ARCNET
TB2-3
COM A OUT
Local Differential ARCNET
TB2-4
COM B OUT
Local Differential ARCNET
TB3-1
RS-232 GND
To red lead on download cable P/N 75267
RS-232 Download
or Printer Port
TB3-2
RS-232 TxD
To black lead on download cable P/N 75267
TB3-3
RS-232 SUPV
Optional Printer Supervision
TB3-4
RS-232 RxD
To green lead on download cable P/N 75267
TB4-1
ARCNET PORT 1A
Secondary Broadband Network (See Note 1)
TB4-2
ARCNET PORT 1B
Secondary Broadband Network (See Note 1)
TB4-3
ARCNET PORT 2A
Secondary Broadband Network (See Note 1)
TB4-4
ARCNET PORT 2B
Secondary Broadband Network (See Note 1)
W1, W2, W3
Factory Jumpers
Factory Use Only or Right (Default OUT)
W4
ARCNET Termination
OPEN = Normal Operation
SHORT = If the ANX is located at the end of the ARCNET bus.
W5
Network Ground Fault
UP: = Supervise Secondary Network for GND FLTs
DOWN or Out: = No Network GND FLT Supervision
SW1-1
Serial Communication
ON = RS-232 115.2 kbits/sec (OFF = defined by CAMWorks
™)
SW1-2 thru SW1-8
Not Used
SW2-1
RING SELECT
Ring/Node Assignment (See Table 3.7.8.1.2)
SW2-2
RING SELECT
Ring/Node Assignment (See Table 3.7.8.1.2)
SW2-3
RING SELECT
Ring/Node Assignment (See Table 3.7.8.1.2)
SW2-4
RING SELECT
Ring/Node Assignment (See Table 3.7.8.1.2)
SW2-5
Not Used
J1
ETHERNET
To FocalPoint or TCP/IP Network Port
Green LED-Communication link established (blinks with message traffic)
Yellow LED-100 Mbps speed (Off - 10Mbps)
J2
Local ARCNET
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX
J4
ARCNET Repeater Connector
Connects to J10 of the RPT-E3
J5
Local ARCNET
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or
ANX
J6
Fiber Port Tx2
From previous node Tx1 Connector
J7
Fiber Port Rx2
From previous node Rx1 Connector
J8
Fiber Port Tx1
To next node Tx2 Connector
J9
Fiber Port Rx1
To next node Rx2 Connector
LED1
REC
Network Reconfiguration
Primary
(Local Network)
LED2
MRC
Network Reconfiguration originating from this node
LED3
DUP
Node’s Network Address is duplicated at another node
LED4
TX
Node is transmitting data to the network
LED5
RX
Node is receiving data from the network
LED6
RST
Node is resetting
LED7
DG
General Network Fault
LED8
REC
Network Reconfiguation
Secondary
Network
LED9
MRC
Network Reconfiguration originating from this node
LED10
DUP
Node’s Network Address is duplicated at another node
LED11
TX
Node is transmitting data to the network
LED12
RX1
Node1 is receiving data from the network
LED13
RX2
Node2 is receiving data from the network
LED14
RST
Node is resetting
LED15
DG
General Network Fault
Table 3.7.8.1.1 ANX-MR-FO Wiring Connections
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...