10
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
Section 1: System Overview
1.1 Description
The Gamewell-FCI E3 Series
®
Expandable Emergency Evacuation System is a multiprocessor
based analog/addressable fire alarm control panel, designed for commercial, industrial and
institutional fire alarm applications. The E3 Series
®
is Listed by Underwriter
’s Laboratories under
Standard UL 864, 9th Edition. It is suitable for the following signaling services:
•
Automatic Fire Detector Alarm
•
Manual Fire Alarm
•
Waterflow Alarm
•
Supervisory
•
Automatic Smoke Alarm, non-coded and master coded operation
•
Releasing Device Service
When the System is configured and installed under the supervision of a Gamewell-FCI factory
trained and certified distributor, the E3 Series complies with the requirements of the following
National Fire Protection Association (NFPA) Standards:
•
NFPA 13 Installation of Sprinkler Systems
•
NFPA 16 Deluge Foam - Water Sprinkler Systems
•
NFPA 72 National Fire Alarm Code:
– Central Station Fire Alarm Systems
– Local Fire Alarm Systems
– Auxiliary Fire Alarm Systems
– Remote Station Fire Alarm Systems
– Proprietary Fire Alarm Systems
1.2 Standard Features
•
Two (2), Class A, Style 6, 7* or Class B, Style 4 Signaling Line Circuits
•
Two (2), Class A, Style Z or
Class B, Style Y Notification Appliance Circuits, 2.0 amp each
•
Alarm, Trouble and Supervisory dry contacts
•
Accommodates 159 Gamewell-FCI Approved, UL
®
Listed compatible analog sensors per
signaling line circuit (ILI-MB-E3 or ILI-S-E3 only).
•
Accommodates 159 Gamewell-FCI Approved,
UL Listed compatible addressable
monitor/control devices per signaling line circuit (ILI-MB-E3 or ILI-S-E3 only)
•
Accommodates 126 Gamewell-FCI Approved,
UL Listed compatible sensors/modules
per signaling line circuit (ILI95-MB-E3 or ILI95-S-E3 only)
•
80-character alphanumeric LCD di
splay (40 characters user-defined)
4100 event history buffer (non-volatile)
•
Power-limited
•
Resettable/non-resettable 2.0
amp @ 24 VDC power output each
•
Alarm verification
•
Walk test
•
Multi-level alarm processing
•
Positive Alarm Sequence (PAS) operation
•
NAC coding
•
Trouble reminder
•
Integral RS-232 port
•
ANX network interface communicates between the
E3 Series fire alarm control panel and the
FocalPoint Graphic Workstation
*Style 7 operation requires System Sensor, M500X Isolator Module (ILI-MB-E3 or ILI-S-E3) or
XP95-LI Line Isolator and XP95-LIB Line Isolator Base (ILI95-MB-E3 or ILI95-S-E3).
UL
®
is a registered trademark of Underwriters Laboratories, Inc.
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...