E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
97
ILI-MB-E3 and ILI95-MB-E3 Connections
E3 Series System Connections
3.1.4 Notification Appliance Circuits
Figure 3.1.4.1 Notification Appliance
Circuits
3.1.5 ILI-MB-E3 and ILI95-MB-E3 Outputs
The ILI-MB-E3 or ILI95-MB-E3 provides output for a Local Energy City Master Box, reversing
polarity output for leased line connection, or Releasing Service.
3.1.6 ILI-MB-E3 and ILI95-MB-E3 Specifications
The following lists the electrical specifications for the ILI-MB-E3 and ILI95-MB-E3.
The ILI-MB-E3 or ILI95-MB-E3 provides two (2), 24
VDC Class A, Style Z or Class B, Style Y notification
appliance circuits. See Figure 3.1.4.1 for wiring
information. See the Compatibility Addendum,
P/N: 9000-0427, for a list of approved compatible
devices.
Wiring Instructions:
NAC 1
– Style Y
TB2-1 (+), TB2-2 ( - )
NAC 2
– Style Y
TB2-5 (+), TB2-6 ( - )
NAC 1
– Style Z
TB2-1 out, TB2-3 return
NAC 2
– Style Z
TB2-5 out, TB2-7 return
TB2-6 out, TB2-8 return
(Polarity markings indicate the polarity of the circuit in
alarm condition). Use UL Listed End of Line Resistor
EOL-N (33K), P/N 4700-0484 for Class B, Style Y
wiring.
Circuit Ratings:
24 VDC (Nom.) FWR
Max. alarm load: - 2.0 amp/circuit
Ground fault test impedance: Zero ohms
Supervised - Power-limited
18 AWG minimum
MDL3 Series Synchronization Modules must be
connected. Special application: See Compatibility
Addendum, P/N 9000-0427 for a list of Gamewell-FCI
approved, UL Listed notification appliances.
Ratings
Master Box (NPL) Polarity Reversal (PL)
Releasing Service
Nominal Voltage
24 VDC
24 VDC
24 VDC
Supervisory Current: .0018 amp
.012 amp
.0005 amp
Alarm Current:
.510 amp (max.)
.012 amp
.700 amp
Line Resistance
35 Ohms (max.)
2 Ohms (max.)
Trip Coil Resistance 14.5 Ohms (max.)
Table 3.1.5.1 ILI-MB-E3 and ILI95-MB-E3 Outputs
Specifications
ILI-MB-E3
ILI95-MB-E3
Operating Voltage:
24 VDC (from PM-9/PM-9G
power supply)
24 VDC (from PM-9/PM-9G
power supply)
Operating Current:
0.081 amp
0.050 amp
Alarm Current:
0.150 amp
0.091 amp
Operating Temperature: 32
° to 120° F (0° to 49° C)
32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93% non-condensing at 90
° F
(32
° C)
0 to 93% non-condensing at 90
° F
(32
° C)
Supervised
Power-limited
EOL
ILI-MB-E3/
ILI95-MB-E3
B (-)
A (-)
A (+)
B (+)
- +
- +
DOTTED LINES INDICATE CLASS A,
STYLE Z WIRING. REMOVE EOL
FOR CLASS A, STYLE Z
OPERATION
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...