168
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
LCD-7100 Remote Display Connections
3.14.4 LCD-7100 Wiring Connections
Table 3.14.4.1 lists the field wiring connections for the LCD-7100.
Designation
Description
Comments
TB1-1
COM-A
Connect to BSM TB5-2 or ILI-MB-E3 or ILI95-MB-E3 TB3-1
(18 AWG min. twisted-pair)
TB1-2
COM B
Connect to BSM TB5-1 or ILI-MB-E3 or ILI95-MB-E3 TB3-2
(18 AWG min. twisted-pair)
TB1-3
Earth GND
Connect to earth ground
TB1-4
Not used
TB1-5
+24 VDC
Connect to BSM TB4-2 or ILI-MB-E3 or ILI95-MB-E3 TB3-6
(16 AWG min. twisted-pair)
TB1-6
24V Common
Connect to BSM TB4-3 or ILI-MB-E3 or ILI95-MB-E3 TB3-7
(16 AWG min. twisted-pair)
Table 3.14.4.1 Remote LCD Display Wiring Connections