E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
43
Cabinets
Installation
2.5.5.2 Cabinet A or AA, 3-Bay, Inner Door Installation
1.
Mount the two (2), ASM-16 sub-assemblies on the inner door and secure with eight (8), #6-32
nuts in each of the two (2), four-hole mounting patterns as shown in Locations 1 and 3 of the
figure below.
2.
Mount the sub-assembly on the inner door and secure with four (4), #6-32 nuts in the four-hole
mounting pattern as shown in Location 2 of the figure below.
3.
Secure the opposite end of the bonding wire to the welded #6 stud on the inner side of the inner
door using the #6 nut as shown in Location 4 of the figure below.
4.
After the panel is wired, use the thumbscrews to secure the inner door to the backbox as shown
in Location 5 of the figure below.
Figure 2.5.5.2.1 Cabinet A or AA, 3-Bay Inner Door Installation
NUT, HEX,
(#6-32")
12 PLACES
BONDING
WIRE
CABINET A, 3-BAY,
INNER DOOR
ASM-16
ASM-16
NGA
2
1
1
2
3
3
1
2
3
1
2
3
1
3
1
2
2
3
THUMBSCREWS
TO SECURE THE
INNER DOOR TO
THE BACKBOX
5
5
4
4
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...