176
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
Section 5: Programming
UL Standard 864 Programming Requirements
System programming is performed via a portable computer and the Gamewell-FCI CAMWorks
™
Configuration. The following menu options are available via the optional LCD-E3 display/keypad
module.
5.1 MAIN LCD-E3 Menu Selections
Table 5.1.1 lists the Main LCD-E3 Menu selection and description.
5.2 WALK / DRILL Menu Selection
Table 5.2.1 lists the Walk / Drill Menu selection and description.
NOTE: NOTICE to users, installers, Authorities Having Jurisdiction (AHJ), and other involved
parties:
This product incorporates field programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th
Edition, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Program Feature
Permitted in UL 864
Possible Settings
Settings Permitted in
UL 864
Trouble Reminder
Yes
Enabled or Disabled
Enabled
Menu Selection
Description
CONFIG. Pressing CONFIG on the main menu automatically opens the
Autoconfig Menu, where automatic configuration of the system is
accomplished. There are two modes:
“Clear and Reconfigure” – Can be us
ed to initialize a completely new
sub-assembly prior to FCP configuration.
“Update SLCs only” This feature pr
ovides the ability to preload the
system with a full configuration, then use Autoconfigure to activate
only those circuit devices that are physically present.
The process can be repeated as new SLC sections are connected or
temporarily removed.
Table 5.1.1 Main LCD-E3 Menu Selections
Menu Selection
Description
Drill ON/OFF Is a simple ON or OFF selection. ON will activate the NACs, while
OFF will deactivate the NACs.
Audible Test
Is a simple ON or OFF selection for an audible walk test. The NACs
will sound twice for a trouble, 3 times for a supervisory signal and 4
times for an alarm.
Table 5.2.1 Walk / Drill Menu Selection
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...