156
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Repeater (RPT-E3) Connections
3.11.5 Repeater-E3 Wiring Connections (Continued)
Table 3.11.5.2 lists the Transmitter Output Power Jumper Settings for the RPT-E3.
Port 1
Port 2
Transmit
Power
J4
J5
J6
J7
J8
J9
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
12.5%
SHORT
OPEN
OPEN
SHORT
OPEN
OPEN
25.0%
OPEN
SHORT
OPEN
OPEN
SHORT
OPEN
37.5%
SHORT
SHORT
OPEN
SHORT
SHORT
OPEN
50.0%
OPEN
OPEN
SHORT
OPEN
OPEN
SHORT
67.5%
SHORT
OPEN
SHORT
SHORT
OPEN
SHORT
75.0%
OPEN
SHORT
SHORT
OPEN
SHORT
SHORT
87.5%
SHORT
SHORT
SHORT
SHORT
SHORT
SHORT
100.0%
Table 3.11.5.2 Transmitter Output Power Jumper Settings