E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
145
Digital Alarm Communicator Transmitter (DACT-E3) Connections
E3 Series System Connections
3.10.2 Telephone Requirements
•
DC Ringer Equivalence Number (REN) = 0.5B
•
AC Ringer Equivalence Number = 1.3
•
Complies with FCC Part 8
The REN is used to determine the quantity of devices that may be connected to the telephone line.
Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5).
To be certain of the number of devices that may be connected to the line, as determined by the total
RENs, contact the Telephone Company to determine the maximum REN for the calling area.
3.10.3 Specifications
The following list the electrical specifications for the DACT-E3.
Operating Voltage:
24 VDC (from PM-9/PM-9G power supply)
Operating Current:
0.018 amp
Alarm Current:
0.018 amp
Operating Temperature: 32
° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing at 90
° F (32° C)
Supervised
Power-limited
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...