E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
99
Intelligent Loop Interface-Main Board Connections
E3 Series System Connections
3.2.1 Intelligent Loop Interface-Main Board (ILI-MB-E3) Wiring
Connections
Field wiring connections for the ILI-MB-E3 are shown in Table 3.2.1.1. All wiring is Power-
limited except the local energy City Box which is non power-limited.
Designation
Description
Comments
TB1-1, TB1-3 +24 V IN
+24 VDC Input from PM-9/PM-9G TB4-1
TB1-2, TB1-4 GND
Common negative from PM-9/PM-9G TB4-2
TB2-1
NAC1 B+
Notification Appliance Circuit 1 (See Note 6)
TB2-2
NAC1 B -
Notification Appliance Circuit 1 (See Note 6)
TB2-3
NAC 1 A+
Notification Appliance Circuit 1 (See Note 6)
TB2-4
NAC 1 A-
Notification Appliance Circuit 1 (See Note 6)
TB2-5
NAC2 B+
Notification Appliance Circuit 2 (See Note 6)
TB2-6
NAC2 B-
Notification Appliance Circuit 2 (See Note 6)
TB2-7
NAC 2 A+
Notification Appliance Circuit 2 (See Note 6)
TB2-8
NAC 2 A-
Notification Appliance Circuit 2 (See Note 6)
TB3-1
AUX RS485 A
Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3 (See Note 3)
TB3-2
AUX RS485 B
Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3 (See Note 3)
TB3-3
Earth Ground
Connect to water pipe ground
TB3-4
Resettable B+
Auxiliary resettable 24 VDC power
TB3-5
GND
Common negative
TB3-6
Non-resettable B+
Auxiliary non-resettable 24 VDC power
TB3-7
GND
Common negative
TB3-8
Municipal Ckt +
Output to Local Energy City Box or Remote Station or Releasing Solenoid -
Non Power-limited (See Note 7)
TB3-9
Municipal Ckt -
Output to Local Energy City Box or Remote Station or Releasing Solenoid
–
Non Power-limited (See Note 7)
TB4-1
SLC 2 A-
SLC 2 Style 6 / 7 Return (See Note 5)
TB4-2
SLC 2 A+
SLC 2 Style 6 / 7 Return (See Note 5)
TB4-3
SLC 2 B-
SLC 2 Style 4 / 6 / 7 Out (See Note 5)
TB4-4
SLC 2 B+
SLC 2 Style 4 /6 / 7 Out (See Note 5)
TB4-5
SLC 1 A-
SLC 1 Style 6 / 7 Return (See Note 5)
TB4-6
SLC 1 A+
SLC 1 Style 6 / 7 Return (See Note 5)
TB4-7
SLC 1 B-
SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB4-8
SLC 1 B+
SLC 1 Style 4 / 6/ 7 Out (See Note 5)
TB5-1
Alarm DC NC
Alarm relay contact, N/C
TB5-2
Alarm DC NO
Alarm relay contact, N/O
TB5-3
Alarm DC Common
Alarm relay contact, Common
TB5-4
Supv DC NC
Supervisory relay contact, N/C
TB5-5
Supv DC NO
Supervisory relay contact, N/O
TB5-6
Supv DC Common
Supervisory relay contact, Common
TB5-7
Trbl DC NC
Trouble relay contact, N/C
TB5-8
Trbl DC NO
Trouble relay contact, N/O
TB5-9
Trbl DC Common
Trouble relay contact, Common
Table 3.2.1.1 ILI-MB-E3 Field Wiring Connections
Содержание Gamewell-FCI E3 Series
Страница 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...
Страница 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...
Страница 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...
Страница 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...
Страница 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...
Страница 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...