INSTALLATION, OPERATING AND

MAINTENANCE INSTRUCTIONS

DAX3FI_MAN01_EN

STAINLESS STEEL

FLAMMABLE GAS DETECTOR

DAX 3F-I

Ver. V1R2

Содержание DAX 3F-I

Страница 1: ...INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS DAX3FI_MAN01_EN STAINLESS STEEL FLAMMABLE GAS DETECTOR DAX 3F I Ver V1R2...

Страница 2: ...o switch off power and declassify the hazardous area before carrying out replacement or modification works on components of the gas detection system Application The DAX 3F I gas detector is suitable f...

Страница 3: ...ty e IIC equipment group II subdivision according to the nature of the explosive GAS atmosphere methane propane ethylene hydrogen acetylene T6 T4 temperature class according to the maximum surface tem...

Страница 4: ...tstone bridge measuring circuit For details of compatible control unit please contact Dalemans The flammable gas detector DAX 3F I comprises the following main parts The sensing head The junction box...

Страница 5: ...n takes place on the active element The heat of reaction on the catalyst layer produces a variation in the resis tance of the active element This resistance variation which is a function of gas concen...

Страница 6: ...5 DAX 3F I Dimensions Figure 3 DAX 3F I mechanical pattern 152 5 45 10 128 5 100 60 166 100 60 43 P C A...

Страница 7: ...sing head may not be modified Do not open the junction box or the sensing head while explosion hazard might be present Only clean or wipe the detector surface with a wet cloth so as to avoid the risk...

Страница 8: ...perts having specialist knowledge of gas dispersion with those who have knowledge of process plant system and equipment involved and with safety and engineering personnel Should you require any furthe...

Страница 9: ...her information Mounting The detector should be mounted flat on a wall and according to the mechanical pattern given in f igure 3 Attach the detector to the wall using the original external mounting b...

Страница 10: ...he control unit For more information about the cross sectional area of the cable and the maximum cable length please refer to the instruction manual of the control unit The overall cable diameter must...

Страница 11: ...ged so that the gap between the insulation and the metallic edge of the terminal connection does not exceed 1 mm distance Equipotential bonding may be provided using either the internal earthing termi...

Страница 12: ...rew the sensing head top using the suitable tool OUT00000113 Replace the sinter metal filter with a new one MEC00000010 Screw up the sensing head top and tighten Make sure the sensing head is still co...

Страница 13: ...r and perform full cali bration Spare parts Article code Bracket mounting kit B O I 0 0 0 0 0 1 4 8 Cable gland Ex e M20 6 12 mm BRASS P R E 0 0 0 0 0 0 2 9 Cable gland Ex e M20 6 12 mm STAINLESS STEE...

Страница 14: ...class 20 C to 70 C for T5 and T4 temperature class Humidity Ambient 20 90 HR Intermittent 10 99 HR Pressure 90 110 kPa Cable cross sectional area 1 5 2 5 mm solid wires Max cable length Refer to the...

Страница 15: ...ent directive March 23 1994 on the approximation of the laws of the member states concerning equipment and protective systems intended for use in potentially explosive atmospheres EN 60079 0 standard...

Страница 16: ...DALEMANS s a rue Jules M lotte 27 B 4350 Remicourt Tel 32 0 19 54 52 36 Fax 32 0 19 54 55 34 info dalemans com www dalemans com OFFICIAL DEALER...