background image

   

UniPOS

 

Gas Detector –     

 71CNG

,

UniPOS

 

,

i

!

           Before use, read 
        the instructions carefully!

Addressable Natural Gas Detector 

Type :71CNG

TECHNICAL SPECIFICATION

ENGLISH

GENERAL DESCRIPTION

The 71CNG detector (fig.1) is applicable for detection of natural gas (methane) in the protected area. The status of the detector is 

indicated with LEDs and sounder.

The 71CNG detector has a signal (communication) and external power interface lines.

The signal loop (communication) interface line is compatible with the IFS7002 fire control panel through the UniTalk private protocol. 

The signal loop (communication) interface power supplies the communication, micro-controller, detection schematics of the device. 

In order to be fully functional, the 71CNG device requires additional external power supply in the range (18 – 30) Vdc, which supplies 

the sounder and Led indication and heating of the sensor. 

The signal loop (communication) interface is protected with a short-circuit isolator.

Both power supplies are galvanic-separated and must not be with common ground. The common ground will not damage the 

standalone operation of the 71CNG, but will affect the communication between the detector and the IFS7002 control panel.

TECHNICAL DATA

Maximum number of  71CNG detectors in the IFS7002 signal loop: 

 

125 pcs.

Supply voltage :

                           - signal loop 

 

 

 

 

 

 

 

(15-30) V DC

                           - external power 

supply 

 

      (18-30) 

DC

Current consumption in Duty mode:                         

                           - signal loop 

 

 

 

 

 

 

 

< 350µA 

                           - external power 

supply 

 

      55 

mA 

Current consumption in Alarm mode :

                           - signal loop 

 

 

 

 

 

 

 

(2±1)mA

                           - external power 

supply 

 

      75 

mA

Sound 

level 

         100dB@1m

Temperature: 

         from 

minus 

5°С 

to 

40°С

Degree 

of 

protection 

        IPX2D

Relative humidity resiatance (no condensation)  

 

 

 

 

≤ 95%

Dimensions 

         (134x36x112)mm

Weight 

          0.115кg.

Construction: 

         ABS

1

02/09.20

02/09.20

ATTENTION !!! OPERATION TO BE DONE IN CASE OF ALARM:

– Put out any flames.
– Close the gas tap or the cylinder.
– Do not turn any  electrical consumers on or off.
– Open all windows and doors to increase ventilation.
– If alarm stops it is necessary to discover the cause and act on consequence.
– If the alarm continues and the cause is not evident or possible to eliminate leave the room
   immediately and call the emergency service.

Fig.1

CONTROL AND INDICATIONS

       The 71CNG detector's functions are indicated through the following LEDs (fig1 pos.1):

green -

 indicates working power supply status of the detector 

 - If the green LED is continuous On - there is properly working power supply

yellow –

 indicates fault and service status. 

 - If the yellow LED is blinking - the gas sensor is in heating (warm-up) procedure for 120 seconds

 - If the yellow LED is continuous On - there is fault in the 71CNG detector

red 

and 

yellow 

– indicates duty and verification mode

 - If both LEDs are continuous On -  a service command is required in the IFS7002 control panel (Menu setup>Initializa-

tion>Check)

 - If both LEDs are blinking simultaneously in a period of 16 sec. - there is fault in the 71CNG detector

red – 

indicates alarm  

 - If the red LED is continuous On - the methane level is over the calibrated trigger level in the device

and

INDICATES

FUNCTIONS

 

Gas Detector –     

 71CNG

INSTALLATION

To mount the 71CNG detector,

please remove front panel.

The detector should be installed vertically at the wall – LEDs indicators are in the top-side 

of the cabinet, the inlet openings are on the bottom side of the cabinet.

-5°С

+40°С

The gas detector must not be mounted:

– Directly above cooking appliances;

– Directly above a sink;

– Adjacent to extractor fans;

– In any outside location;

– Where the environment conditions are outside 

   of operational specification.

Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, 

http://www.unipos-bg.com

Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, 

http://www.unipos-bg.com