38
L1= 5m(max)
The wiring length between the upper controller and drive CN1 should be 5m or less.
L2=250mm(max)
The wiring length between each drives CN1 should be 250mm or less.
Terminal resistance
Connect the terminal resistor between 43pin and 44pin of CN1 to the last drive and to the upper controller.
Figure 4.4.1 Multi-station connection example
The wiring between the drives are shown as above. And daisy-chained connection should be performed between the drive
connector CN1 and the upper controller.
[Communication address setting]
When using multi-station communication, set the different communication address for each drive according to the following
steps. There are two setting methods: by set panel and dedicated software.
Input 24V control power supply after wiring, then operate as the following steps For wiring, refer to section 4.1[Wiring
diagram].
Communication speed
57.6 kbps
Data bit
8 bit
Peer bit
None
Stop bit
1 bit
Alarm detection
CRC16-CCITT
Transmission data
8 bit binary
Data length
35 bytes or less