![Hitachi FSG Series Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/hitachi/fsg-series/fsg-series_technical-catalogue_139455074.webp)
4
/2
CAPACITIES AND SELECTION DATA
4.1.
SYSTEM SELECTION PROCEDURE
The following system procedure is giving a sample
regarding unit selection system, indicating how to use all
parameters showed in this chapter.
4.1.1.
SELECTION UNIT FEATURES
Considering the building distribution, the possible indoor unit
position and the available air flow distribution, select the unit
features that is giving the best efficiency and comfort to
each room.
Decide the Outdoor Unit position getting easy service
maintenance and easy refrigerant pipe installation.
Use the information showed in the following subchapters:
§
For Operation Space possibilities: Subchapter 4.2
Operation Space.
§
For Air Flow distribution: Subchapter 4.10 Temperature
Distribution Diagrams.
§
For Noise Characteristics: Subchapter 4.11 Sound Data
§
For Outdoor Unit position: Subchapter 4.2.8 Outdoor Unit
§
For CH-Box position: Chapter 12.9.2
§
Piping length and lift range: Chapter 13
If duct type unit is selected, the fan performance for duct
calculation should be considered, as Subchapter 4.9 shows.
The units are designed with three possible static pressure
ranges in order to adapt it to all installation necessities.
As indicated in chapter 1, the Set-Free system enable the
outdoor unit to be up to 30% smaller capacity when
compared with the current split Air Conditioning systems.
The diagram shows a typical building with a morning peak
heat load on the east zone equivalent to a 6HP unit.
In the afternoon a peak occurs on the west zone equivalent
to a 7HP unit.
Therefore, a conventional system would require total
installed plant of 6HP + 7HP = 13HP. The maximum
simultaneous load on the whole building occurs at noon and
is equal to 10HP of unit capacity. A Set-Free System of
10HP can therefore be selected, and this capacity can be
directed either to the east or west zone as dictated by the
system controls.
Saving in installed plant = (6.5-5) / 6.5 x 100 = 23%!!!
Example of Air Conditioning for Building
Therefore, the maximum indoor unit capacity combined with
outdoor unit should be carefully considered for correct
indoor unit distribution at each building
For three pipes systems, FXG, the units distribution is more
flexible, because of each indoor unit can operate at different
mode, cooling or heating. At the same time, is possible to
combine several indoor units with the same CH-Box when
all the space need the same operation mode, or all indoor
units will be used in the same room, in order to get better Air
flow distribution. Do not forget to consider that option during
installation design.
4.1.2.
SELECTION GUIDE
The following example is giving the method for indoor and
outdoor units selection of Set-Free system. The same
system can be used for FSG, FSG1, FXG and FXG1.
*
Step 1: Determine the system requirements
Calculate the cooling capacity and heating capacity of each
indoor unit according to the following conditions:
Total Load for each room
Room
Item
1
2
3
1+2+3
Estimated
Cooling Load
kW
2.75
4.24
5.35
12.34
Estimated
Heating Load
kW
2.90
4.60
6.00
13.50
Temperature Condition
Cooling
Heating
Outdoor Air Inlet
Dry Bulb: 30.0ºC
Outdoor Air Inlet
Dry Bulb: -1ºC
Wet Bulb: 0ºC
Indoor Air Inlet
Dry Bulb: 27,0ºC
Wet Bulb: 19.5ºC
Indoor Air Inlet
Dry Bulb: 20ºC
Equivalent piping length between Outdoor unit
and farther Indoor unit
60 m
Piping Lift between Outdoor Unit and Indoor
Unit
25 m
Load of East Zone
Total Load
Load of West Zone
Loa
d
Time
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...