ELECTRICAL WIRING
15
/13
Unit
Name of Dip
Switch
Mark
Setting Before
Shipment
Function
Refrigerant Cycle
DSW1
ON
For setting refrigerant cycle address of outdoor unit. Set the
DSW1 not to overlap the setting of other outdoor units in the
same H-LINK system
Indoor
Unit
End Terminal
Resistance
DSW10 - 1P
ON
1
2
For matching impedance of transmission circuit. Set the DSW10
according to the quantity of outdoor units in the H-LINK system.
Setting of End Terminal Resistance
Before shipment, No.1 pin of DSW10 is set at the “ON” side.
In the case that the outdoor units quantity in the same H-link is 2
or more, set No.1 pin of DSW10 at the “OFF” side from the 2nd
unit. If only one outdoor unit is used, no setting is required.
Refrigerant Cycle
DSW5
ON
For setting refrigerant cycle address of indoor unit. Set the DSW5
corresponding to the address of outdoor unit in the same
refrigerant cycle.
Outdoor
Unit
Indoor Unit Address
RSW
0
For setting indoor unit address. Set the RSW not to overlap the
setting of other indoor units in the same refrigerant cycle. (If not
set, the automatic address function is performed.)
15.5
WIRE SIZES
§
Electrical Wiring Connection
Field Minimum Wire Sizes for Power Source
Power Source Cable Size
Transmitting Cable Size
Model
Power Source
Max. Current
EN60 335-1
É
É
É
É
MLFC
Ê
Ê
Ê
Ê
EN60 335-1
É
É
É
É
MLFC
Ê
Ê
Ê
Ê
All Indoor Units
220-240V/1
f
/50Hz
5 A
0.75 mm²
0.5 mm²
RAS-5FSG
18 A
2.5 mm²
0.75 mm²
RAS-8FSG
32 A
4 mm²
2 mm²
RAS-10FSG
36 A
6 mm²
3.5 mm²
RAS-16FSG
63 A
10 mm²
8 mm²
RAS-20FSG
81 A
-
14 mm²
RAS-24FSG1
74 A
-
8 mm²
RAS-30FSG1
87 A
-
14 mm²
RAS-20FXG1
64 A
-
8 mm²
RAS-30FXG1
380-415V/3
f
/50Hz
87
-
14 mm²
0.75 mm²
0.5 mm²
?
NOTE:
– Follow local codes and regulations when selecting
field wires.
– The above wire sizes marked with
É
are selected at
the maximum current of the unit according to the
European Standard, EN60 335-1. Use the wires which
are not lighter than the ordinary polychloroprene
sheathed flexible cord (code designation H05RN-F).
– The above wire sizes marked with
Ê
are selected at
the maximum current of the unit according to the wire,
MLFC (Flame Retardant Polyflex Wire) manufactured
by HITACHI Cable Ltd. Japan.
– In the case that the power cables are connected in
series, add each unit maximum current and select
wires below.
– The earth cable size complied with local code:
IEC 245, No. 571.
Selection according to
EN60 335-1
Selection according to MLFC
(at cable Temp. Of 60 ºC)
Current i (A)
Wire Size
(mm²)
Current i (A)
Wire Size
(mm²)
I
£
6
0.75
I
£
15
0.5
6 < i
£
10
1
15
<
i
£
18
0.75
10 < i
£
16
1.5
18
<
i
£
24
1.25
16 < i
£
25
2.5
24
<
i
£
34
2
25 < i
£
32
4
34
<
i
£
47
3.5
32 < i
£
40
6
47
<
i
£
62
5.5
40 < i
£
63
10
62
<
i
£
78
8
63 < i
Ë
78
<
i
£
112
14
112
<
i
£
147
22
Ë
In the case that current exceeds 63 A do not connect cables in
series
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...