UNITS INSTALLATION
12
/21
12.8
RAS (OUTDOOR UNIT)
12.8.1
INSTALLATION LOCATION (5 TO 10 HP)
n
Installation Place
§
Install the outdoor unit in a place where there is
adequate space around the unit for operating and
maintenance as shown below.
*
Add the half of dimension h1 to 300mm for air intake space of rear
side, when the wall of rear side is higher than 500mm.
*
Add the half of dimension h2 to 1500 for air intake space of front
side when the wall front side is higher than 1500 mm
§
Install the outdoor unit where a good ventilation is
available.
§
Install the outdoor unit where it is in the shade or it will
not be exposed to direct sunshine or direct radiation
from high temperature heat source.
§
Install the outdoor unit where the falling ice from the
unit will not create a hazard, as in the case of
installation on top of a building where ice may fall
down on the pedestrians.
§
Install the outdoor unit where the sound or discharge
air from the outdoor unit does not affect neighbors or
environment.
§
Check to ensure that the foundation is flat and
sufficiently strong.
§
Do not install the outdoor unit where dust or other
contamination could block the outdoor heat
exchanger.
§
When installing the outdoor unit in snow-covered
areas, mount the field-supplied hoods on the top of the
outdoor unit and the inlet side of the heat exchanger.
§
Do not install the outdoor unit where there are high-
levels of oil mist, salty air or aggressive gases such as
sulfur.
§
Do not install the outdoor unit where electromagnetic
waves are directly radiated to the electrical box and
inverter components.
§
Install the outdoor unit as far as practical at least 3
meters from the electromagnetic wave radiation, as
electronic noise can cause miss-operation of the unit.
?
NOTE:
In certain cases, a fuse may be blown and the system
my stop in high electro-magnetic turbulence
environment.
In certain cases, the system can get an alarm in high
electro-magnetic turbulence environment. In such
case, stop and start the system to clear the alarm.
&
CAUTION:
Aluminum fins have very sharp edges. Pay attention
to the fins to avoid any injury.
?
NOTE:
Install the outdoor unit on a roof or in an area where
people except service engineers can not touch the
outdoor unit.
■
Basic Space
12.8.2
INSTALLATION SPACE FOR SINGLE UNIT
§
In case that the front side and either of the sides are
open.
Rear Side Intake Space
Front Side Intake Space
(Top View)
(mm)
Air Intake
Side View
No Limit to Wall Height
(mm)
Front
Side
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...