UNITS INSTALLATION
12
/19
12.7
RPF (FLOOR TYPE) / RPFI (FLOOR CONCEALED TYPE)
12.7.1
FACTORY-SUPPLIED ACCESSORIES
(Models: RPF(I)1.0/2.5)
Accessory
Qty
Purpose
Adjustment Bolt
for Intallation
4
For Adjusting the Flat
Level of the Unit
Ring Core
2
Screw
2
PC-P1HE
12.7.2
INITIAL CHECK
§
Install the indoor unit with a proper clearance around it
for operation and maintenance as shown in Service
Access panel.
RPF
RPFI
Provide a space so that air can flow smoothly
-
Service Access Panel
Provide a service access door or panel as shown
below.
(Space around Indoor Unit)
Size
Model
A
B
RPFI-1.0
1260
RPFI-1.5
1380
RPFI-2.0
RPFI-2.5
620
1634
Consider the air distribution from the indoor unit to the
space of the room, and select a suitable location so
that uniform air temperature in the room can be
obtained.
Check to ensure that the foundation is flat, level and
sufficiently strong.
It is recommended that a service access panel for floor
concealed type indoor units be provided. The access
panel must be fixed with screw(s) so that service
engineer(s) only is accessible.
12.7.3
INSTALLATION
1. Check to ensure the fixing position of the unit as shown
below.
Wall
Wall
More Than 300
More Than 300
630
Wall
Ceiling
Upward Air Outlet
Short Flexible
Duct
640
Wall
More Than 240
More Than 240
Service Space
for Electrical
Box
Piping Space
Front Air Outlet
620
More Than 240
More Than 240
Service Space for
Electrical Box
Piping Space
Ceiling
Unit
(Inside)
Service
Access Panel
Service
Access Panel
B
A
Floor
Fixing onto Floor using wood screws (2-M8)
(View from top Side)
Fixing onto Wall
(View from front Side)
Fixing onto Floor using wood screws (4-M5)
(View from top Side)
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...