REFRIGERANT PIPING AND REFRIGERANT CHARGE
13
/47
13.8.
CAUTION ON REFRIGERANT LEAKAGE
Specifiers/installers have responsibility to follow local codes
and regulation which specify safety requirements against
refrigerant leakage
13.8.1.
MAXIMUM PERMISSIBLE
CONCENTRATION OF HCFC GAS
The refrigerant R407C, charged in the SET-FREE FSG
system, is an incombustible and non-toxic gas. However, if
leakage occurs and gas fills a room, it may cause
suffocation.
The maximum permissible concentration of HCFC gas,
R407C in air is 0.3 kg/m³, according to the refrigeration and
air conditioning facility standard (KHK S 0010) by the KHK
(High Pressure Gas Protection Association) Japan.
Therefore, some effective measure must be taken to lower
the R407C concentration in air below 0.3 kg/m³, in case of
leakage.
13.8.2.
CALCULATION OF REFRIGERANT
CONCENTRATION
1. Calculate the total quantity of refrigerant R (kg) charged
in the system connecting all the indoor units of rooms to
be air-conditioned.
2. Calculate the room Volume V (m³) of each room.
3. Calculate the refrigerant concentration C (kg/m³) of the
room according to the following equation:
R
— = C
V
R: Total Quantity of Charged Refrigerant (kg)
V: Room Volume (m³)
C: Refrigerant Concentration (
£
0.31* kg/m³ for
R407C)
* Use this value for reference only, since this value is not
fixed yet.
Room
R (kg)
V (m³)
C (kg/m³)
Countermeasure
A
30
150
0.2
-
B
65
500
0.13
-
C
35
100
0.35
0.06 m² Opening
D
35
100
0.35
0.06 m² Opening
C+D
35
200
0.175
-
E
35
50
0.7
2 m³/min
13.8.3.
COUNTERMEASURE FOR REFRIGERANT
LEAKAGE ACCORDING TO KHK
STANDARD
The facility shall be arranged as follows referring to the KHK
standards, so that the refrigerant concentration will be
bellow 0.3 kg/m³.
1. Provide a shutterless opening which will allow fresh air to
circulate into the room.
2. Provide a doorless opening of 0.15% or more size to the
floor area.
3. Provide a Ventilator, Linked with a gas leak detector, of
0.4 m³/min or more ventilating capacity per Japanese
Refrigeration Ton (=compressor displacement m³/h/8.5)
of the air conditioning system utilizing refrigerant).
O.U. Model
Ton
O.U. Model
Ton
RAS-5FSG
2.49
–
–
RAS-8FSG
4.32
RAS-8FXG
3.74
RAS-10FSG
4.64
RAS-10FXG
4.01
RAS-16FSG
6.69
RAS-20FSG
8.53
RAS-20FXG1
7.45
RAS-24FSG1
8.72
RAS-30FSG1
10.55
RAS-30FXG1
10.55
4. Pay a special attention to the place, such as a basement,
etc., where refrigerant can stay, since refrigerant is
heavier than air.
Opening: 0.06 m²
Gas Leak Detector
Ventilator 2 m³/min
Floor
40 m²
Floor
40 m²
Floor 200 m²
Floor 60 m²
Floor
20 m²
He
ig
ht
2.5
m
System B Outdoor Unit
System A Outdoor Unit
System A
Refrigerant: 35 kg
E
D
C
B
A
System B
Refrigerant: 30 kg
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...