INSTALLATION OF OPTIONAL REMOTE CONTROLLER
16
/3
Standard Capable distance for receiving Signal of Air
Panel for Wireless Control.
(Example: In Case of 4-way Cassette Type)
Condition:
§
Typical office room
§
No electronic lamp within 1 m around receiver part of
Panel or Receiver Kit.
Standard Capable distance for receiving Signal of Air
Panel for Wireless Control.
(View from Above)
(Example: In Case of 4-way Cassette Type)
Condition:
§
Operation of Wireless Remote Control Switch from
position; 2.6 m from ceiling level, 1 m from floor level.
§
Typical office room
§
No electronic lamp within 1 m around receiver part of
Panel or Receiver Kit.
16.1
INSTALLATION OF REMOTE CONTROL SWITCH <PC-P1HE>
16.1.1
BEFORE INSTALLATION
Check the contents and the number of the accessories in
the packing.
Remote Control
Switch, for
Operation Control
2 screws
Ø4x16L
For fixing the
Holding Bracket
onto the wall
1 Band
For fixing Cable
to Ring Core
Ring Core
16.1.2
INSTALLATION SPACE
In case of installing the controllers in vertical line, keep a
distance more than 10 mm between the controllers
vertically. If the distance is insufficient, the front cover of the
controller can not open wide enough
Ceiling
Floor
Ceiling
Floor
Capable Range for Receiving Signal
Capable Range for Receiving Signal
1 - Direction of receiver
1 - Direction of receiver
More Than 10 mm
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...