AVAILABLE OPTIONAL FUNCTIONS
24. Power Supply ON/OFF 2 [
@!
@!
@!
@!
]
This function is utilized to start the unit operation again
automatically when the power supply is recovered after
the power failure over 2 seconds.
The standard unit is started operation again automatically
with all the same operating conditions such as operation
mode, etc. in case of the power failure within 2 seconds.
(The compressor unit is started operation again after
three minutes guard in addition to 2 seconds power
failure as a maximum.)
?
NOTE:
In case of power failure during the unit stoppage, the
unit is stopped after recovering the power supply.
25. Ventilation Mode
(Total Heat Exchange Model) [
-
-
-
-
]
This function is utilized to set the ventilation mode of the
total heat exchanger.
The setting condition and the ventilatrion mode are as
shown below.
Setting
Condition
Ventilation Mode
Contents
00
Automatic Ventilation
Selecting effective ventilation mode
(Total Heat Exchanging Ventilation or
Bypass Ventilation) for energy saving
by detecting the temperature difference
between the outdoor temperature and
the room temperature.
01
Total Heat Exchanging
Ventilation
The Heat Exchanging is performed
continuously when the total Heat
Exchanger is operated.
02
Bypass Ventilation
The Heat Exchanging is not performed
continuously when the total Heat
Exchanger is operated.
26. Increasing supply Air Volume
(Total Heat Exchange Model) [
-
-
-
-
]
This function is utilized to increase the supply air volume
with the one-step high tap of the fan motor for supply air
during operation of the total heat exchanger, make the
room pressure higher than the surrounded room with the
increased supply air volume and prevent polluted air and
smell from entering into the room.
The setting air flow model by remote control switch and
the actual air flow of the total heat exchanger when
setting this function are as shown below.
Setting Air Flow Mode by
Remote Control Switch
Air Flow of Total Heat
Exchanger
LOW
MED
MED
HIGH
HIGH
HIGH
?
NOTE:
In case that the setting air flow mode by the remote
control switch is "HIGH", the air flow of the total heat
exchanger is "HIGH" even when this function is set.
27. With Humidifier (Only Indication)
(Total Heat Exchanger Model) [
-!
-!
-!
-!
]
This function is utilized to control the total heat exchanger
with the humidifier. However, in case of the total heat
exchanger of SET-FREE, the humidifier is not attached.
Do not set this function. When this function is not set, the
control of the humidifier is not performed.
28. Precooling/Preheating Period
(Total Heat Exchange Model) [
-"
-"
-"
-"
]
This function is utilized to delay the start-up of the total
heat exchanger operation.
The setting condition and the delay period of operation
start-up are as shown below.
Setting Condition
Delaying period of Operation
Start-up
00
0 minutes
01
30 minutes
02
60 minutes
29. Not Prepared
30. Automatic Setting for OFF Timer [
.
.
.
.
]
This function is utilized to set the OFF timer function
automatically when the unit is started by the remote
control switch. During operation with the automatic OFF
timer setting function, the cancellation of the OFF timer
and the changing of the setting period for OFF timer can
not be performed. However, the OFF timer function is
cancelled when the unit is stopped.
When the unit is operated again after stoppage, the
setting period for OFF timer is the period set by the
optional setting.
The setting condition and the setting period for OFF timer
are as shown below.
Setting Condition
Setting Period for OFF Timer
00
Function Invalid
01
1 Hour
02
2 Hours
03
3 Hours
~
~
22
22 Hours
23
23 Hours
24
24 Hours
?
NOTE:
This function is cancelled when connecting with the
CS-NET, and 7-day Timer, controlled by Remote
Control.
31. Remote Control Main-Sub Setting [
.
.
.
.
]
This function is utilized when two remote control switches
are installed in one system.
Set one remote control switch to "Main", and another
remote control switch to "Sub"
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...