TROUBLESHOOTING
18
/19
18.6
SELF CHECKING OF PCB'S USING REMOTE CONTROL SWITCH
Following troubleshooting procedure is utilized for function
test of PCB's in the Indoor Unit and Outdoor Unit
Stop Operation
.
Press
PCB Check Mode
.
Press both
switches for 3 seconds
(ex.) indication of Unit No. "
"
Indication of Unit Number
After
7 seconds
Operating Automatic PCB
Check
Result
After Approx. 5 sec. (Max 30 Sec. in case
of transmission failure between Indoor
Unit and Outdoor Unit)
Max. 3 types of abnormalities indicated.
Abnormality (1)
After 1 sec.
¯¯¯¯
Abnormality (2)
After 1 sec.
¯¯¯¯
Abnormality (3)
After
1 second
To next page
RUN/STOP
Indi-
cation
Contents
00
Normal
Abnormality (Open-circuit, Shor-circuit, etc.) in circuit for:
01
Intake Air Temp. Thermistor
02
Discharge Air. Temp. Thermistor
03
Liquid Pipe Temp. Thermistor
04
Remote Thermistor abnormality
05
Gas Pipe Temp. Thermistor
06
Remote Sensor
08
Transmission of Central Station
0A
EEPROM
Ob
Zero Cross Input Failure
EE
Transmission of indoor during this
checking operation
Indoor
Unit PCB
07
Transmission of Outdoor Unit
F4
ITO Input Failure
F5
PSH Input failure
F6
Protection Signal Detection Circuit
F7
Phase Detection
F8
Transmission of Inverter
FA
High Pressure Sensor
Fb
Comp. Discharge Gas Temp. Thermistor
FC
Low pressure Sensor
Fd
Heat Exchanger Evaporation Temp.
Thermistor
FF
Ambient Air Temp. Thermistor
Outdoo
r Uni
t PCB
Contents
TEMP
CHECK
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...