/6
AVAILABLE OPTIONAL FUNCTIONS
10.1.5.
CONTROL BY FIELD-SUPPLIED ROOM
THERMOSTAT
In the case that a field-supplied room thermostat instead of
the inlet thermistor of the Indoor Unit is used, connect wires
as shown below. The required parts are shown in item
10.1.2.
(In case of "Room Thermostat (Cooling) function 01" Input
to #2 and #3 of CN3 and "Room Thermostat (Heating)
function 02" Input to #1 and #2 of CN3)
Cooling
Operation:
Compressor is ON by closing terminals 2 and
3 at CN3.
Compressor is OFF by opening terminals 2
and 3 at CN3.
Heating
Operation:
Compressor is ON by closing terminals 1 and
2 at CN3.
Compressor is OFF by opening terminals 1
and 2 at CN3
Component
Manufactured or Specifications
Thermostat
Equivalent of YAMAKATE R7031P005,
R7031Q005
?
NOTE:
-
When a field-Supplied room thermostat is used, select
the specified thermostat as below:
Contactor Load: DC 12V
Differential:
more than 1.5 degree
-
Do not use a thermostat utilizing mercury.
-
The Remote Control switch must remain connected to
the unit. When the power supply is restored, the Unit
must be started by pressing the RUN button. The
compressor will then operate under the control of the
field supplied thermostat. All other functions are
controlled by the Remote Control in the normal way.
10.1.6.
REMOTE TEMPERATURE SENSOR
CONTROL
By using an optional remote temperature sensor, the
following are available:
1. The unit is controlled by the average temperature of the
inlet thermistor and remote temperature sensor.
2. In the case that the discharge air temperature exceeds
60 °C, the fan speed increases from "Medium" to "High"
or "Low" to "Medium"
?
NOTE:
1. The remote temperature sensor can not be used
together with the remote control thermistor (Refer to
the item 10.3.2)
2. During the heating operation, "Heating Temperature
Calibration" is automatically cancelled (Refer to the
item 10.3.2.
3. In case of using this remote sensor, select the location
for installing it as follows:
-
Where the average temperature of the room can be
detected.
-
Where the thermistor (sensor) is not exposed to the
sun light directly.
-
Where a heat source is not near it.
-
Where outdoor air do not affect the room
temperature when opening and closing doors, etc.
Thermostat
Temperature
Increase
Indoor
Unit
PCB
3P Connector
PCB
THM1
THM4
Inlet Air Temperature
Remote
Temperature Sensor
Remote
Control
Switch
Содержание FSG Series
Страница 2: ......
Страница 4: ......
Страница 13: ...3 57 7 1 7 ...
Страница 14: ......
Страница 110: ......
Страница 116: ......
Страница 146: ......
Страница 159: ...CONTROL SYSTEM 9 13 9 6 STANDARD OPERATION SEQUENCE 9 6 1 COOLING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Страница 161: ...CONTROL SYSTEM 9 15 9 6 2 COOLING MAINLY COOLING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Страница 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Страница 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Страница 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Страница 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Страница 169: ...CONTROL SYSTEM 9 23 9 6 6 HEATING MAINLY HEATING OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Страница 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Страница 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Страница 172: ...9 26 CONTROL SYSTEM 9 7 STANDARD CONTROL FUNCTIONS 9 7 1 FREEZING PROTECTION CONTROL DURING COOLING OR DRY OPERATION ...
Страница 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Страница 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Страница 228: ......
Страница 229: ...3 57 167 7 21 7 ...
Страница 230: ......
Страница 287: ...REFRIGERANT PIPING AND REFRIGERANT CHARGE 13 11 GAS LINE LIQUID LINE E 152S E 162M1 E 202M1 E 242S E 302S ...
Страница 324: ......
Страница 344: ......
Страница 376: ......
Страница 423: ......
Страница 424: ...TCGB0023 rev 0 04 04 Printed in Spain ...